The following table explains the effect of the Channel Data Modifier:
Channel Data
Modifier
Description
1
Perform EU conversion and store result in both FIFO buffer and
Current Value Table.
2*
Leave measurement as voltage and store result in both FIFO and CVT.
3
Perform EU conversion and store result in CVT only.
4*
Leave measurement as voltage and store in CVT only.
5
Perform EU conversion and store result in FIFO only.
6*
Leave measurement as voltage and store in FIFO only.
7*
Leave measurement as voltage and do not store result in either
FIFO or CVT. Use as dummy channel set.
* Limit Checking (CALCulate:LIMit:
…
) cannot be performed on channels that are not
converted to Engineering Units.
•
Both the standard and relative channel specification modes can be mixed within a
Scan List definition. For example:
ROUTe:SEQuence:DEFine LIST1,(@100:115, 6(00:15))
specifies that the readings taken on channels 0 through 15 are to be converted into
engineering units and stored in both the FIFO data buffer and the Current Value
Table (CVT). In addition, channels 0 through 15 are to be read and the raw
voltage values are to be added to the FIFO buffer. The FIFO will contain 16
converted readings and 16 voltage readings. The CVT will contain a converted
reading for channels 0 through 15.
•
After using
ROUTe:SEQuence:DEFine
, use
[SENSe:]FUNCtion:
…
commands to
set each channel to a specific function and range.
•
Related Commands:
ROUTe:SCAN
•
*RST Condition: Scan List 1 =
(@100:163)
, Scan Lists 2 through 4 have no
channels assigned to them.
Usage
ROUT:SEQ:DEF LIST2,(@100:131)
EU conversion to both FIFO and CVT
(standard).
ROUT:SEQ:DEF ALL,(@100:131)
Same channels and conversion as above but
to all four Scan Lists.
ROUT:SEQ:DEF LIST1,(@2(00:31)
Voltage readings to both FIFO and CVT
(relative channel specification using
Channel Modifier.
ROUTe
Chapter 5
HP E1313/E1413 Command Reference 223