ROUTe
The
ROUTe
subsystem controls which of four Scan Lists will be executed at the
next trigger event, and defines the channel content of each Scan List.
Subsystem Syntax
ROUTe
:SCAN <
scan_list
>
:SEQuence:
:DEFine <
scan_list
>,(@<
ch_list
>)
:DEFine? <
scan_list
>[,<
mode
>]
:POINts? <
scan_list
>
ROUTe:SCAN
ROUTe:SCAN <
scan_list
>
establishes which of the four Scan Lists will be used
for measurement scans.
Parameters
Parameter
Name
Parameter
Type
Range of
Values
Default
Units
<
scan_list
>
discrete (string)
LIST1 | LIST2 | LIST3 | LIST4 | LISTL
none
Comments
•
When
ROUTe:SCAN
is
LISTL
, the module will automatically sequence through
the scan lists specified by
ROUTe:SEQuence:DEFine LISTL,(@<
ch_list
>)
.
LISTL Notes
1. When
ROUTe:SCAN
selects
LISTL
(List-of-Lists), each scan list it specifies
must contain at least 6 channels.
2.
LISTL
can only be selected while module is in Trigger Idle State (not
INITiated
).
3. When
CALCulate:AVERage:STATe
is
ON
,
LISTL
is not allowed.
•
Normally, the specified scan list number becomes effective when the Trigger
System moves from the Initiated State to the Wait-for-Trigger State. If
ROUTe:SCAN LIST1-LIST4
is executed after this point, it will become effective
for the next scan. If
INITiate:CONTinuous
is
ON
and
TRIGger:SOURce
is
IMMediate
,
ROUTe:SCAN
will generate an error. Refer to Figure 5-3 for
scanning event sequence.
•
Related Commands:
ABORt
,
INITiate:
…
commands,
ROUTe:SEQuence:DEFine
•
*RST Condition:
ROUTe:SCAN LIST1
Usage
ROUT:SCAN LIST3
The next scan list executed will be LIST3.
ROUTe
220 HP E1313/E1413 Command Reference
Chapter 5
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com