73
Honeywell, Issue 9
March 2007
XLS80e Fire Alarm Control Panels
2a
Select the required release mode:
AUTO - release configuration will apply
when the sensors signal an alarm (the
AUTO/MANUAL/OFF selection is set to
AUTO).
MANUAL - release configuration will apply
when the Manual Release is operated (the
AUTO/MANUAL/OFF selection is set to
either AUTO or MANUAL).
IMMEDIATE - release configuration will
apply when Immediate Release input is
activated (release is immediate and
overrides ABORT, OFF and HOLD).
Options 1 and 3 allow the HOLD input to
override the release, options 2 and 4 allow
the release to override the HOLD input (for
use with HOLD mode IRI,
Section 7.8
).
IMMEDIATE RELEASE IS FOR USE
DURING SYSTEM COMMISSIONING
ONLY AND MUST NEVER BE
INSTALLED IN THE MANNED ROOM.
Select whether the release will operate for
a soak period, after which it will turn off, or
whether it will operate indefinitely (until the
panel is reset). The soak period is
configured in the Panel Settings menus and
is the same for all Extinguishing Systems
on the panel.
IF INPUT WAS ALARM:
7.6.2.5 Extinguishing System
1
Select which Extinguishing System the
Control Matrix entry applies to.
CAUTION:
This product is not compliant
with EN 12094-1.
EN
12094-1
!
EN
12094-1
!
Fire extinguishing installations in
Europe are required to be certified as
compliant to this standard.