Honeywell, Issue 9
March 2007
XLS80e Fire Alarm Control Panels
TO ENSURE THAT THE PANEL COMPLIES WITH
EN54 REQUIREMENTS REGARDING ACTIVATION
OF ALARMS IN EVENT OF FIRE:
7.1.1 EN54 Requirements
Every HONEYWELL panel is factory-
configured with two default Control Matrix
entries.
Any alarm input anywhere on the system will
cause all bell devices, and those internal
sounder circuits configured as sounders, to
operate immediately in ‘steady’ mode (i.e. they
are switched on to sound continuously).
The EVACUATE function will operate all BELL
circuits.
Note
: Sounders 3 and 4 will only be activated
if they are configured as sounder
outputs and not relays.
IMPORTANT - EN54 COMPLIANCE
The default entries may not be appropriate to
your installation. However, if you delete either
or both defaults it is then your responsibility to
ensure that the installation complies with the
requirements of EN54-2.
<EVACUATE
PUSHBUTTON> activates: <ALL BELLS>
IS THE DEFAULT CONTROL MATRIX ENTRY.
I.E.
OR
AN ADDITIONAL ENTRY IS ALSO FACTORY-
CONFIGURED:
I.E.
It is your
responsibility to
ensure compliance
with EN54-2.
IF YOU DELETE A DEFAULT ENTRY:
<ANY INPUT>
activates: <ALL BELLS>
Control Matrix Configuration 2
INPUT: ALARM:
ANY ZONE
OUTPUT:
ALL ZONES, BELL
=edit/delete *=new entry X=cancel
Control Matrix Configuration 1
INPUT:
EVACUATE P/Button
OUTPUT:
ALL ZONES, BELL
=edit/delete *=new entry X=cancel
‘
’