15
XLS80e Fire Alarm Control Panels
Honeywell, Issue 9
March 2007
Limitations of the Auto-learn Method
If the auto-learn method is used on an
incomplete system it will give the false
impression that the system is fully operational.
In such cases, the auto-learnt data MUST be
checked carefully against the system
specification.
During the auto-learn procedure, input
module logical types are set to defaults.
Modules not conforming to the defaults must
be re-configured using the Manual Learn or
Configure Individual Device procedures.
3.7
Configure Group of Devices
On a configured panel, this configuration
method allows a group of devices at consecutive
addresses to be deleted or all set to the same
type.
Refer to
Section 5.2
.
3.8
Configure Individual Device
This configuration method requires the user to
select each loop device and set all parameters
and conditions, e.g. sensitivity, time-of-day,
device text, etc. appropriate to it.
It can also be used to add further details to the
configuration resulting from the auto-learn
method.
Refer to
Section 5.1
.
Note
: Sensitivity and alarm verification delay
recommendations are given in
Section 13
.
Caution - a false indication
of a fully-functional system
is given if the Auto-learn
procedure is used on an
incomplete system.
Input module types are
set to defaults during the
Auto-learn procedure
and may require manual
re-configuration.