106
Honeywell, Issue 9
March 2007
XLS80e Fire Alarm Control Panels
11.21 Alarm Coincidence
This menu may be Panel Settings option 21
or 22, depending upon whether the Day/Night
Modes configuration option is present.
Select the Zones level to be edited (where
‘level’ indicates the position on the Control
Matrix ‘Multiple Zone Coincidence Rule’ menu).
For the current level, enter the number of
zones that must be in alarm at the Control
Matrix input. Confirm changes, then repeat this
procedure for each level you want to configure;
press
to exit the Zones level setting option.
Select the Devices level to be edited (where
‘level’ indicates the position on the Control
Matrix ‘Select Coincidence Rule’ menu).
For the current level, enter the number of
devices that must be in alarm at the Control
Matrix input. Confirm changes, then if required
repeat this procedure for the remaining level;
press
to exit the Devices level setting
option.
Select the scope of Device Coincidence when
the Control Matrix input zone selection is ANY
ZONE:
a. The devices must be on the same panel,
or (networked panels) on any panel of the
network. This is the default.
b. The devices must be in the same zone.
Select the scope of Device Coincidence when
the Control Matrix input zone selection is a
range of cells:
a. Two or more devices in alarm in the same
cell. This is the default.
b. Two or more devices in alarm within the
selected range of cells.
NUMERIC
ENTRY, THEN
WHEN ALL
REQUIRED
LEVELS ARE
SET
NUMERIC
ENTRY, THEN
WHEN ALL
REQUIRED
LEVELS ARE
SET
It is recommended that the co-
incidence number increases
with the level number.
It is recommended that the co-
incidence number increases
with the level number.
Panel Settings
ALARM COINCIDENCE levels for DEVICES:
Coincidence threshold for level n
(3-99):
Press to confirm changes, X to cancel
nn
Panel Settings
Operation of COINCIDENCE for 'ANY ZONE'
Control Matrix Input Rules:
1:
2:Same ZONE always
Same PANEL or NETWORK
Panel Settings
18:DIAGNOSTIC RS232 Port setup
19:Remote Fire Output options
20:DAY/NIGHT MODES configuration
21:EXTINGUISHING System Common Options
22:
ALARM COINCIDENCE levels
WHEN
REQUIRED
OPTION IS
SELECTED
Panel Settings
Operation of COINCIDENCE for Control
Matrix Input Rules with RANGE OF CELLS:
1:
2:Coincidence spans RANGE of CELLs
Must be in same CELL