85
Honeywell, Issue 9
March 2007
XLS80e Fire Alarm Control Panels
9
Time-of-Day Programming
This facility lets you modify the function of the
panel at certain times of day. The major time-
of-day controlled functions are:
a. Sensor sensitivity (
Section 5.1.2.7
).
b. Control Matrix actions (
Section 7.6.2.2
).
c. Cancelling all disablement conditions on the
panel (non EN54-2 compliant)
(
Section 11.7
).
This section describes how to edit and use a
time-of-day program.
Note
: A Control Matrix entry can be used to
control the Disable and Enable functions,
independent of the Disablement Panel
Settings (see
Section 7.7, Disablement/
Enablement Function
).
Up to seven time-of-day programs can be in
operation in any one panel. The programs
operate completely independently of each
other. Any particular sensor sensitivity or
Control Matrix action may be modified
according to
one
of the programs.
9.1
Time-of-day Program Editing
The Time-of-day editing procedure is common
to all these applications. A typical program
consists of one or two daily periods specified by
start and end times, with an optional alternative
for weekends. For example, this display:
indicates that from Mondays to Fridays the
‘active’ periods of the program are 08:30 to
10:40 inclusive, and 18:00 to 06:00 the
following day. On Saturdays and Sundays the
periods are 08:30 to 10:40 and 18:00 to 07:00
the following day.
When editing a Time-of-day program that
applies to the Disablement Panel Settings (see
Section 11.7
), the ‘start’ times of each period
are irrelevant and are omitted from the display,
which then looks like this:
EN54-2: 9.1.2
Disablement and
re-enablement MUST be
a manual operation.
-MTWTF-
0830-1040
1800-0600
S - - - - -S
0830-1040
1800-0700
-MTWTF-
1040
0600
S - - - - -S
1040
0700