XLS80e Fire Alarm Control Panels
Honeywell, Issue 9
March 2007
12 User Menu at Level 3 Access
Note
: Menu options that can be accessed at
level 2 are described in the XLS80e
Series Operating Manual 997-474.
Some of the menus normally available at
access level 2 include options that can only
be accessed at a higher access level (see
opposite). This section describes these
options.
Access 3
* * *
Access 3A
* * * * *
12.1 Control Output Tests
These tests let you select an individual Control
Output and activate it without putting the whole
system into alarm or walk test mode. The
following can be tested:
a. CMX modules.
b. Local sounder circuits (1, 2, and also 3 and
4 if so configured in hardware).
c. Local relay circuits (3 and 4, if so configured
in hardware).
d. Loop sounders and boosters.
From the Test Menu, select the Control Output/
Sounder Test option. If you are not already at
access level 3 (i.e. the User tab is displayed
instead of the Service tab), you are prompted
to enter the access 3 passcode.
(ONLY DISPLAYED IF YOU ARE NOT ALREADY
AT ACCESS LEVEL 3)
TO NEXT PAGE