104
Honeywell, Issue 9
March 2007
XLS80e Fire Alarm Control Panels
11.19 Day/Night Modes Configuration
This menu option is only available if a Fire
Output has been configured (see
Section 11.18
). The settings allow
configuration of the Day Mode two-stage
investigation time, which delays operation of
the fire output(s) (does
not
delay sounders,
use the Control Matrix to do this). The first-
stage time is configured in seconds and is
initiated by an alarm while Day Mode is active
(set by the DAY MODE pushbutton; Day Mode
can also be configured to occur automatically
by a time-of-day program). The second-stage
time is configured in minutes and is initiated
when the EXTEND DELAY pushbutton is
pressed while the first-stage time is active; it
replaces (is NOT added to) the first-stage time.
Set the Day Mode delays as follows:
1
Enter the required first-stage investigation
time.
2
Enter the required second-stage
investigation time.
3
Select whether a change of state at Input 2
of the panel results in a change from Day
Mode to Night Mode (option 2), or a Day/
Night Mode change in either direction
(option 3) or has no effect (option 1).
4
Select whether Day Mode can only be set
active by the DAY MODE pushbutton, or
whether a time-of-day program will set Day
Mode at specified times of day.
IF MANUAL, OR
AUTO AT
SPECIFIED TIMES:
(AT
CONFIRM
PROMPT)
TO NEXT PAGE
NUMERIC
ENTRY, THEN
NUMERIC
ENTRY, THEN
EN54-2: 9.1.2
Disablement and
re-enablement MUST be
a manual operation at
access level 2.
5
If a time-of-day program is to be used, set
the required times in the manner described
in
Section 9
. In this case there are only two
time fields for each day set, not a pair of
start and end times. Also, there is no ‘level’
adjustment and no ‘Manual Override’.
6