65
Honeywell, Issue 9
March 2007
XLS80e Fire Alarm Control Panels
IF CURRENT PANEL:
Restricted by Type
7
Either select ANY INPUT DEVICE TYPE
(includes Virtual Input Points) or restrict to
one of the types in the list.
Options 9 to 11 are provided for use with
the Extinguishing System, although they
are available for any ‘Alarm’ input. Item 10
can be used in the case that a manual
release switch configured as an MCP is
only to be operable if there is an alarm. The
switch must be in the same zone as the
sensor (ensure there are no other MCPs
in the zone).
Note:
There is no ‘Type’ for Gas Sensors. Gas
Sensors which are configured for
Technical Alarm are included with Fire
Alarms by the Control Matrix. Use the
Individual Device, Zone(s) or Cell(s)
input selections to specify Gas
Sensor(s) and to separate out Control
Matrix actions dependent upon
Technical Alarms or Fire Alarms.
Device Coincidence
Note:
These options are only displayed if the
following are both true: Option 1 (Single
Zone) is set in step 6 and the option
selected in step 7 is not option 9, 10 or
11 (since these already include a co-
incidence).
Note:
For device coincidence to occur the
devices in alarm must normally be in the
same zone or cell. However,
for cells
only
the devices can be in a range of
cells if the panel setting is so configured
(see
Section 11.21
).
8
Select the required option. SINGLE DEVICE
and 2 Devices are always available; the
remaining options are only displayed if they
are configured in the panel settings
(
Section 11.21
). In the illustration, ‘n’ and ‘p’
each represent a number in the range 3-99.
IMPORTANT
To avoid configuring MCPs into the
coincidence group you must configure two
separate Control Matrix entries:
i
The first entry should define the MCP input
type (e.g. ‘ANY MANUAL CALL POINT’) as
‘SINGLE DEVICE’ (no coincidence).
ii
The second entry should define an input
type (for example ‘ANY ANALOGUE
SENSOR’, which includes HEAT, ION,
OPT, LASR and MULT sensors) to which
coincidence will apply.
EN54-2: 7.1.4
CAUTION:
Do not include MCPs in a
coincidence group.
If ‘ANY Zone’ is selected in step 12, then for device
coincidence to occur the devices must:
either
be in the same panel (or network)
or
be in the same zone
depending upon the ‘ANY ZONE’ panel setting
(
Section 11.21
).
The use of zone coincidence and
restricted-by-type in the same
Control Matrix entry is not
supported.