XLS80e Fire Alarm Control Panels
7
Select the required effect of a new alarm.
8
Select whether type SPRINKLER acts in
the same way as type MCP.
11.20 Extinguishing System
This option sets various Extinguishing System
parameters.
EXTINGUISHING SYSTEM SETTINGS TAKE
EFFECT
NUMERIC ENTRY
NUMERIC ENTRY
NUMERIC ENTRY
FROM PREVIOUS PAGE
Panel Settings
CANCEL Investigation delay if NEW ALARM
during 2nd Investigation Period?
1:
2:NO
YES
Panel Settings
ALARM from Module type SPRINKLER
over-rides Investigation Delay?
1:
2:YES
NO
DAY MODE SETTINGS TAKE EFFECT
1
Enter the required default activation time
delay period. This period can be edited in
the Control Matrix, however the default is
used to differentiate between the AHJ and
NYC HOLD modes (the former uses the
default configured here, the latter uses a
time longer than the default).
2
Enter the required number of seconds
before the release is activated at which the
PAUSE occurs in the ULI and IRI HOLD
modes.
3
Enter the flood duration time. This time is
used if the ‘Turn off Release after SOAK
period’ option is selected on an Alarm
Control Matrix entry.
CAUTION:
This product is not compliant
with EN 12094-1.
EN
12094-1
!
EN
12094-1
!
Fire extinguishing installations in
Europe are required to be certified as
compliant to this standard.