TABLE 1—CNAP NETWORK VARIABLES.
NOTE: THE FOLLOWING INPUTS/OUTPUTS ARE COMMONLY USED WITH THE NETWORK VIA DATA-
SHARING.
Variable Name
Description
Point Information
Discharge Air Temperature
Used for datasharing to zone controllers
Physical analog input on VAV
(Control Number 1)
to indicate supply air temperature
controller data shared to zone
available for zone heating or cooling.
controllers.
Outdoor Air Temperature
Outdoor air temperature datashared
Physical analog input on source
(Control Number 5)
among controllers from one source
controller datashared to remote
point.
analog inputs on destination
controllers.
Zone Occupied Status
Summary of all VAV terminal box
User assigns to remote analog
(Control Number 80)
control (W7620) occupied status
input on the W7600. The Zone Occu-
information used to force the VAV
pied Status must be datashared from the
control into occupied mode when
W7620 VAV Box controllers to the
a zone has demand:
W7600 (many to one logical OR operat-
1 = unoccupied
ion).
2 = occupied
4 = unoccupied override
8 = warmup
16 = continuous unoccupied
NOTE: Numbers other than those
listed indicate mixed variations
of VAV box status (occupied
unoccupied, warmup, etc.).
RestoreShed flag
Bump discharge air cooling
Remote digital input.
(Control Number 165)
setpoint upward to shed cooling load.
Network Occupied Flag
Used to force the VAV control
Remote digital input.
(Control Number 166)
to the occupied mode via
network communication.
Network Controlled Digital
Used for TOD control of lighting,
Destination point for ON/OFF
Outputs
exhaust fans, etc.
control via network. A remote digital
(Control Numbers 248-255)
input for the Network Controlled
Digital Output is automatically config-
ured by the software when a remote dig-
ital output is configured by the user.
NETWORK STATUS INDICATORS OF THE AIR HANDLING UNIT
Heat/Cool Mode
Indicates current mode of operation
Heat or Cool indicated.
of the W7600 VAV control.
VAV Occupied Flag
Indicates OCC/UNOCC status of the
OCCUP or UNOCC indicated.
VAV air handling unit and is a
digital point type for use as a
network datashare
source
point.
AM Warmup Status
Indicates when the W7600 VAV
WARM or No WARM indicated.
control determines that morning
warmup is engaged.
Econo Allowed Flag
Indicates the economizer enable
ECON or No ECON indicated.
function so only one outdoor
enthalpy sensor needs to be used on the
network. Used as a
source
point for
datasharing to other controllers.
TOD Occ Flag
Indicates OCC/UNOCC status of the
OCCUP or UNOCC indicated.
time of day schedule only
in the VAV
AHU controller. Used as a network
datashare
source
point.
Cool Setpoint
Indicates current discharge air cooling
Numerical value indicated.
setpoint including reset.
PM7600B
PM7600B INPUT AND OUTPUT OPTIONS