Control
Value
Control
Dependent
Dependent
Number
Variable Required
Required
Number
Variable Required
Value Required
HEATING CONTROL
To disable heating control, set HEAT_STG =0; otherwise, set HEAT_STG to 1-6 for number of stages.
[CV] HEAT_TYPE
0, 1, or 2
See below.
With 0, 1, or 2
[CV] TEMP_RATE_LIM
1
°
-20
°
F/minute
1
[AI] DA_TMP
Must be
configured.
[CV] HEAT_STG
1-6
196-201 [DO] HEAT1-6
Equal
HEAT_STGs
[CV] HEAT_TIME
0-3780 seconds
[SP] PRG_DAH_SP or
60
°
to 130
°
F
12
[AI] DAH_SP
Set
PRG_DAH_SP
to Unprog.,
0
°
F or -18
°
C.
[SP] PRG_DAH_CB or
1
°
to 50
°
F
13
[AI] DAH_CB
Set
PRG_DAH_CB
to Unprog. or 0.
With 1
[CV] MOD_HEAT_DELAY
0-180 seconds
[CV] HEAT_MOTOR_SPEED
30-160 seconds
212-213 [DO] HEAT+, HEAT-
Must be
configured.
With 2
[CV] MOD_HEAT_DELAY
0-180 seconds
54
[AO] A_HEAT
Must be
configured.
[CV] HEAT_STG
Must equal 1.
[CV] HEAT_RESET_TYPE
0, 1, 2, 3, or 4
See below.
0 to disable
None
N/A
With 1, 2, 3, or 4
[SP] HMAX_RESET
50
°
to 150
°
F
[SP] HSTART_RESET
0
°
to 200
°
F
[SP] HEND_RESET
0
°
to 200
°
F
With 1
4
[AI] SP_TMP
Must be
configured.
With 2
5
[AI] OD_TMP
With 3
51
[AO] A_FAN
With 4
7
[AI] RA_TMP
[CV] AUTO_CHANGE
0 or 1
None
N/A
COOLING CONTROL
To disable cooling control, set COOL_STG = 0; otherwise, set COOL_STG to 1-12 for number of stages.
[CV] COOL_TYPE
0, 1, or 2
See below.
With 0, 1, or 2
[CV] TEMP_RATE_LIM
1
°
-20
°
F/minute
1
[AI] DA_TMP
Must be
configured.
[CV] COOL_STG
1-12
VAV CONFIGURATION REQUIREMENTS (continued)
PM7600B
PM7600B INPUT AND OUTPUT OPTIONS