63-4309—2
56
Failure
Special schedule parameters
lost.
Symptoms
Special (Holiday) Schedules Have
Been Lost
displayed on the
S7600A.
Cause
Checksum error in special sched-
ules parameter database.
W7600A-F Action
W7600A-F control functions con-
tinue normally but special sched-
ules are rendered inoperative.
Remedies
Reconfigure all special schedules
using existing archived database
from ZM7601/ZM7603 software.
File group in ZM7601/ZM7603
Software to download to
W7600A-F is
Schedules.
Failure
Access code lost.
Symptoms
Access Codes Have Been Lost
displayed on the S7600A.
Cause
Checksum error in S7600A Key-
board Display Module access
code configuration database.
W7600A-F Action
W7600A-F control functions con-
tinue normally and bypass and
program access codes are set to
0000.
Remedies
Reconfigure access codes using
existing archived database from
ZM7601/ZM7603 Software. File
group in ZM7601/ZM7603 Soft-
ware to download to W7600A-F
is
Config.
Failure
System alarm priority configu-
ration file lost.
Symptoms
Alarm Priority Config Has Been
Lost
displayed on the S7600A.
Cause
Checksum error in system alarm
priority parameter database.
W7600A-F control functions con-
tinue normally. All system alarms
are sent onto the CNAP network
as priority 90.
Remedies
Reconfigure access codes using
existing archived database from
ZM7601/ZM7603 Software. File
group in ZM7601/ZM7603 Soft-
ware to download W7600A-F is
All Files or the selected indepen-
dent file Alarm Priority Configu-
ration.
Failure
System setpoint configuration
file lost.
Symptoms
Setpoint File (FP) Lost, Setpoint
File (B) Lost or Setpoint File
(SW): Lost
displayed on S7600A.
Cause
Checksum error in system setpoint
parameter database.
W7600A-F Action
W7600A-F control functions con-
tinue based on default setopints
in the base control algorithm (if
available).
Remedies
Reconfigure all setpoints in the
original database using ZM7601/
ZM7603 Software. File group to
download to W7600 is
Setpoints.
Failure
Application model configura-
tion lost.
Symptoms
Application Model Config Lost
displayed on S7600A.
Cause
Checksum error in parameter da-
tabase.
Remedy
Reconfigure controller or copy
sample of controller using
ZM7601/ZM7603 Software.
Download
All Files
to W7600.
Home and Building Control
Home and Building Control
Helping You Control Your World
Honeywell Inc.
Honeywell Limited—Honeywell Limitée