19
63-4309—2
ANALOG INPUTS (continued)
S7600
Control
Point Name
Label
Number
Functional Description
Return Velocity
R_VELP
19
Return Air Velocity Pressure Signal, in inches water column,
Pressure
(in. wc.). Applicable to PM7600B, Version 2.0 or later.
Return Static
R_STAT
20
Return Air Static Pressure Signal, in inches water column,
Pressure
(in. wc.). To be used for alarm and Shutdown only, not for control
of Return Fan. Applicable to PM7600B, Version 2.0 or later.
Return Velocity
R_VEL
21
Return Air Flow Velocity Signal, in fpm, from a sensor such as
a hot-wire anemometer. Applicable to PM7600B,
Version 2.0 or later.
Supply Velocity
S_VELP
22
Supply Air Flow Velocity Pressure in inches water column,
Pressure
(in. wc.). Applicable to PM7600B, Version 2.0 or later.
DIGITAL INPUTS
S7600
W7600 Input
Point Name
Label
Control Number
Functional Description
Proof of Condenser
CNDFLO
128
ACTIVE =
Normal operation.
Water Flow
INACTIVE =
Turn on alarm digital output; turn off all
other outputs and send alarm message to
S7600.
NOTE: The W7600 must be reset if a Condenser
Water Flow Failure occurs.
High Pressure Safety
HP1
129
INACTIVE =
Normal operation.
Switch Compressor 1
ACTIVE =
Turn on alarm digital output and send alarm
message to S7600. Turn off Compressor 1
and its unloader; control without Compres-
sor 1.
NOTE: The W7600 must be reset if a High Pressure
Safety occurs.
High Pressure Safety
HP2
130
As with HP1, lock out Compressor 2.
Switch Compressor 2
High Pressure Safety
HP3
131
As with HP1, lock out Compressor 3.
Switch Compressor 3
High Pressure Safety
HP4
132
As with HP1, lock out Compressor 4.
Switch Compressor 4
Compressor 1 Failure
CMP_F1
133
INACTIVE =
Normal operation.
ACTIVE =
Turn on alarm digital output and send alarm
message to S7600. Turn off Compressor 1
and its unloader; control without Compres-
sor 1.
NOTE: The W7600 must be reset if a Compressor
Failure occurs.
Compressor 2 Failure
CMP_F2
134
As with CMP_F1, lock out Compressor 2.
Compressor 3 Failure
CMP_F3
135
As with CMP_F1, lock out Compressor 3.
Compressor 4 Failure
CMP_F4
136
As with CMP_F1, lock out Compressor.
Compressor 1 Oil Pressure
OIL_F1
137
INACTIVE =
Normal operation.
ACTIVE =
Turn on alarm digital output and send alarm
message to S7600. Turn off Compressor 1
and its unloader; control without Compres-
sor 1.
NOTE: The W7600 must be reset if a Compressor Oil
Pressure Failure occurs.
PM7600B
PM7600B INPUT AND OUTPUT OPTIONS