Mechanical Cooling
COOL_LOCKOUT
When the Mechanical Cooling Lockout Sensor
45
°
F
Lockout Setpoint
is below this value, all mechanical cooling is
locked out. One degree accuracy, 10 to 70
°
F. A
value of Unprogrammed (or 0
°
F only)
disables this function.
Airflow Fail Delay
AIR_FLOW_FL_DLY
Delay from turning on the fan until
10 seconds
Airflow Failure, Dirty Filter, and Freezestat
are sensed. Failures are ignored when fan is
off. One second accuracy, 0-255 seconds.
Duct High Static Limit
HIGH_STATIC_LIM
Above this pressure limit, control is de-
5 inches
energized, alarm digital output turns on and an
alarm message is sent to the S7600. One-tenth
inch accuracy from 1.0 to 10 in. wc.
Duct High Static Duration
HIGH_STATIC_DUR
Control allows Duct Static Pressure above
9 seconds
Duct High Static Limit for a number of
continuous time periods before alarming and
de-energizing system. Three second time
period programmable, 0-765 seconds.
Low Discharge Air Limit
LO_DA_LIM
At or below alarm limit, the W7600 will send
35
°
F
an alarm message to the S7600 and turn off
all outputs.
Range = 10-50
°
F.
Discharge Low
LO_DA_DUR
Control allows temperature at Low Discharge
45 seconds
Limit Duration
Air Limit for a number of continuous time
periods before alarming and de-energizing
system. Fifteen second time period
programmable, 0-3825 seconds.
Discharge Air
TEMP_RATE_LIM
When the Discharge Air Temperature
5
°
F/minute
Temperature Rate of
changes faster than the programmed value,
Change
additional cooling or heating capacity is
prevented from operating.
Range = 0 to 20
°
F/minute.
Discharge Pressure
PRESS_RATE_LIM
The programmed value is the limit allowed in
2 inches
Rate of Change
the derivative portion of the total error used in
per minute
the pressure control calculations. Effective only
when the derivative gain for pressure control
is unequal to zero. Range 0 to 5 in. wc/min.
Digital Input Debounce
DEB_TIME0_
Control to ignore a digital input for this
0
DEB_TIME36
debounce time to avoid nuisance alarms.
One second accuracy, 0-255 seconds.
High Speed Fan Minimum
HI_MIN_ON
Defines minimum time high-speed fan digital
On Time
output will be energized. Range = 1-20 minutes.
(Two-speed fan control.)
Warm-up Delay Time
WU_DLY
When mode changes from unoccupied to
occupied, control will delay
WARMUP_DELAY seconds before deter-
mining if warm-up sensor is below warm-up
setpoint, thus enabling warm-up mode.
Recommended
Variable Name
Variable Label
Functional Description/Program Options
Value
PM7600B
PM7600B INPUT AND OUTPUT OPTIONS
Mechanical Cooling
LOCKOUT_SENS
Use to select the sensor used for mechanical
0
Lockout Sensor
cooling lockout:
0 = None
1 = Outdoor Air Temperature (OD_TMP)
2 = Condenser Inlet Temperature
(CNDTMP)
CONFIGURATION PARAMETERS (continued)