63-4309—2
28
Control
Value
Control
Dependent
Dependent
Number
Variable Required
Required
Number
Variable Required
Value Required
COOLING CONTROL (continued)
[CV] COOL_TYPE
With 0, 1, or 2
178-189 [DO] COOL1-12
Equal
(continued)
(continued)
COOL_STGs
[CV] COOL_TIME
0-3780 seconds
[CV] UNLOAD_TIME
0-3780 seconds
[SP] PRG_DAC_SP or
30
°
to 90
°
F
8
[AI] DAC_SP
Set
PRG_DAC_SP
to Unprog., 0
°
F
or 18
°
C.
[SP] PRG_DAC_CB or
1
°
to 50
°
F
9
[AI] DAC_CB
Set
PRG_DAC_CB
to Unprog. or 0.
With 1
[CV] MOD_COOL_DELAY
0-180 seconds
[CV] COOL_MOTOR_SPEED
30-160 seconds
210-211 [DO] COOL+, COOL-
Must be
configured.
With 2
[CV] COOL_STG
Must equal 1.
[CV] MOD_COOL_DELAY
0-180 seconds
53
[AO] A_COOL
Must be
configured.
[CV] COOL_RESET_TYPE
0, 1, 2, 3, or 4
See below.
0 to disable
None
N/A
With 1, 2, 3, or 4
[SP] MAX_RESET
20
°
to 100
°
F
[SP] START_RESET
0
°
to 200
°
F
[SP] END_RESET
0
°
to 200
°
F
With 1
4
[AI] SP_TMP
Must be
With 2
5
[AI] OD_TMP
configured.
With 3
51
[AO] A_FAN
With 4
7
[AI] RA_TMP
[CV] COOL_LOCKOUT
0 to disable or
None
N/A
10
°
to 70
°
F
[CV] COOL_STG
1-12
[CV] LOCKOUT_SENS
1-2
[CV] LOCKOUT_SENS
0, 1, 2
See below.
0 to disable
None
N/A
1
5
[AI] OD_TMP
Must be
configured.
2
3
[AI] CNDTMP
[CV] CND_COMP_DEL
0 to disable or
None
N/A
1-255 seconds
178
[DO] COOL1
Must be
configured.
214
[DO] CNDPMP
[CV] COMP_NUM [ ]
COMPR/
Must include same
N/A
UNLOADER
compressor and loader
ARRAY
sequence as the actual
equipment being controlled.
VAV CONFIGURATION REQUIREMENTS (continued)
PM7600B
PM7600B INPUT AND OUTPUT OPTIONS
Содержание PM7600B
Страница 44: ...63 4309 2 44 NOTES PM7600B PROGRAMMING ...