63-4309—2
24
Economizer Motor Close
1
ECON-
208
OFF =
No action.
ON =
Drive valve or damper toward closed position (air
or water economizer applications).
VAV Box Open
VBOX+
209
OFF =
No action.
ON =
Signal to VAV box damper to fully open for
morning warm-up (heat enable function) and night
setback (optional with W7620 applications).
Cool Load
COOL+
210
OFF =
No action.
(Floating Output)
1
ON =
Load cooling capacity by stage.
Cool Unload
COOL-
211
OFF =
No action.
(Floating Output)
1
ON =
Unload cooling capacity by stage.
Heat Load
HEAT+
212
OFF =
No action.
(Floating Output)
1
ON =
Load heating capacity by stage.
Heat Unload
HEAT-
213
OFF =
No action.
(Floating Output)
1
ON =
Unload heating capacity by stage.
Condenser Pump
CNDPMP
214
OFF =
Condenser pump off.
ON =
Condenser pump on.
Occupied Mode
OCCUP
215
OFF =
Annunciate unoccupied mode.
ON =
Annunciate occupied mode.
Condenser Water Bypass Valve
BP_VLV
216
OFF =
Condenser Water Bypass Valve is closed or closing.
ON =
Condenser Water Bypass Valve is open or opening.
Low Speed Fan
FAN_LO
217
OFF =
Low Speed Fan is off.
ON =
Low Speed Fan is on.
High Speed Fan
FAN_HI
218
OFF =
High Speed Fan is off.
ON =
High Speed Fan is on.
Return Fan
RETFAN
219
Return Fan Start/Stop Output.
Start Stop
Preheat Stage
PREHT1
220
On/Off Stage of Preheat.
Preheat Plus
PREHT+
222
PreHeat Floating Motor Open Signal.
Preheat Minus
PREHT-
223
PreHeat Floating Motor Close Signal.
Ret Fan Plus
RETFN+
224
Return Air Floating Motor Open Signal.
Ret Fan Minus
RETFN-
225
Return Air Floating Motor Close Signal.
1
Analog outputs configured as digital outputs cannot be used for floating control.
DIGITAL OUTPUTS (continued)
PM7600B
PM7600B INPUT AND OUTPUT OPTIONS
S7600
Control
Point Name
Label
Number
Functional Description
Supply Motor Close
SUPLY-
204
OFF =
No action.
(Floating Output)
1
ON =
Drive vanes closed to decrease air volume.
Proof of Airflow
AIR_OK
205
OFF =
Airflow has not been proven.
ON =
Airflow has been proven. The fan digital output
is on and either airflow digital input (if configured)
is on or velocity pressure analog input (if configured)
is above the velocity pressure low limit.
Outdoor Air Damper
OD_DMP
206
OFF =
Outdoor air damper is closed or closing.
ON =
Outdoor air damper is open or opening.
Economizer Motor Open
ECON+
207
OFF =
No action.
(Floating Output)
1
ON =
Drive valve or damper toward open position (air
or water economizer applications).