63-4309—2
14
SETPOINT PARAMETERS
The variables listed below may be programmed by using the ZM7601 Configuration Tool Software package or the
S7600 Keyboard Display Module.
Rec-
ommended
Variable Name
Variable Label
Functional Description/Program Options
Value
Access Code
ACC_CODE1-
Programmed on Controller configuration screen.
ACC_CODE4
Four digit access code required from S7600
to enter program or bypass mode.
Range = 0-9.
Programmed Discharge Air
PRG_DAC_SP
Discharge air temperature cooling setpoint from
55
°
F
Cool Temperature Setpoint
S7600. To use Q7601 Setpoint Module, set value
to Unprogrammed or 0 with the PC or SPECIAL
on the S7600. One degree accuracy.
Range = 33
°
F to 90
°
F.
Programmed Discharge Air
PRG_DAC_CB
Discharge air cooling control band setpoint from
4
°
F
Cool Control Band
1
S7600. To use the Q7601 Setpoint Module, set
value to Unprogrammed or 0 with the PC or
SPECIAL on the S7600. One degree accuracy.
Range = 1
°
to 50
°
F.
Start Discharge Air
START_RESET
Value determines temperature when discharge
74
°
F
Cooling Reset
air cooling reset begins. One degree accuracy.
Range = 0
°
to 200
°
F.
End Discharge Air
END_RESET
Value determines temperature when discharge
68
°
F
Cooling Reset
air cooling reset is at maximum. One degree
accuracy.
Range = 0
°
to 200
°
F.
Discharge Air Cooling
MAX_RESET
Setpoint used for discharge air cooling when the
60
°
F
Reset Setpoint
cooling reset sensor is at or beyond END_RESET.
One degree accuracy.
Range = 20
°
to 100
°
F
Economizer Minimum
MIN_ECONO_POS
Programmable for modulating economizer
10%
control only. One percent accuracy.
Range = 0% (fully closed) to 100% (fully open).
Economizer Offset
ECON_OFFSET
Minimum offset between sensors
10
°
F
that allows the economizer to turn on. This
variable is required when ECON_SELECT
has been programmed to 3.
Range = 0
°
to 100
°
F.
Programmed Static
PRG_PRES_SP
Duct static pressure setpoint from S7600. To use
3.0 inches
Pressure Setpoint
Q7601 Setpoint Module, set value to Unprogram-
med or 0, one-tenth in. wc accuracy.
Range = 0.0-10.0 in. wc.
Programmed Static Pressure
PRG_PRES_CB
Duct static pressure control band setpoint from
2.0 inches
Control Band
1
S7600. To use Q7601 Setpoint Module, set value
to Unprogrammed or 0, one-tenth in. wc accuracy.
Range = 0.2-10.0 in. wc.
1
With floating and modulating control, dead band is
±
20% of programmed value for control band.
PM7600B