25
63-4309—2
Input
Variable
Control
Point Name
Label
Number
Description
Network Controlled Digital Output 1
N_DO_1
248
Remote input via network
OFF = De-energized
On = Energized
Network Controlled Digital Output 2
N_DO_2
249
Remote input via network
OFF = De-energized
ON = Energized
Network Controlled Digital Output 3
N_DO_3
250
Remote input via network
OFF = De-energized
ON = Energized
Network Controlled Digital Output 4
N_DO_4
251
Remote input via network
OFF = De-energized
ON = Energized
Network Controlled Digital Output 5
N_DO_5
252
Remote input via network
OFF = De-energized
ON = Energized
Network Controlled Digital Output 6
N_DO_6
253
Remote input via network
OFF = De-energized
ON = Energized
Network Controlled Digital Output 7
N_DO_7
254
Remote input via network
OFF = De-energized
ON = Energized
Network Controlled Digital Output 8
N_DO_8
255
Remote input via network
OFF = De-energized
ON = Energized
(Network Controlled Digital Input 1) with the same name.
The CNAP No Response Timer for the remote digital
input must be configured by the user.
The control algo-
rithm of the W7600 VAV controller uses the state of the
Network Controlled Digital Input to toggle the Network
Controlled Digital output ON or OFF. The NIU actually
uses the Remote Digital Input associated with the Network
Contolled Digital Output as the destination point for the
datasharing operation. The Network Controlled Digital
Input can be viewed in the digital inputs summary of the
configuration software and in the View Status window
while on line with the site.
NETWORK CONTROLLED DIGITAL OUTPUTS
Configure physical digital outputs to receive ON/OFF
instructions via the network. Datasharing configuration of
the Q7640 Network Interface Unit is also required for this
function.
Configuration of Network Controlled Digital Outputs
A datasharing pair must be configured in the Network
Interface Unit for this feature. When a Network Controlled
Digital Output is configured in the W7600 VAV AHU
controller (e.g., Network Controlled Digital Output 1) the
software will automatically configure a remote digital input
PM7600B
PM7600B INPUT AND OUTPUT OPTIONS