23
63-4309—2
PM7600B
PM7600B INPUT AND OUTPUT OPTIONS
DIGITAL OUTPUTS
S7600
Control
Point Name
Label
Number
Functional Description
Compressor or Unloader Stage 1
COOL1
178
OFF =
Cooling stage 1 off.
ON =
Cooling stage 1 on.
Compressor or Unloader Stage 2
COOL2
179
OFF =
Cooling stage 2 off.
ON =
Cooling stage 2 on.
Compressor or Unloader Stage 3
COOL3
180
OFF =
Cooling stage 3 off.
ON =
Cooling stage 3 on.
Compressor or Unloader Stage 4
COOL4
181
OFF =
Cooling stage 4 off.
ON =
Cooling stage 4 on.
Compressor or Unloader Stage 5
COOL5
182
OFF =
Cooling stage 5 off.
ON =
Cooling stage 5 on.
Compressor or Unloader Stage 6
COOL6
183
OFF =
Cooling stage 6 off.
ON =
Cooling stage 6 on.
Compressor or Unloader Stage 7
COOL7
184
OFF =
Cooling stage 7 off.
ON =
Cooling stage 7 on.
Compressor or Unloader Stage 8
COOL8
185
OFF =
Cooling stage 8 off.
ON =
Cooling stage 8 on.
Compressor or Unloader Stage 9
COOL9
186
OFF =
Cooling stage 9 off.
ON =
Cooling stage 9 on.
Compressor or Unloader Stage 10 COOL10
187
OFF =
Cooling stage 10 off.
ON =
Cooling stage 10 on.
Compressor or Unloader Stage 11 COOL11
188
OFF =
Cooling stage 11 off.
ON =
Cooling stage 11 on.
Compressor or Unloader Stage 12 COOL12
189
OFF =
Cooling stage 12 off.
ON =
Cooling stage 12 on.
Liquid Line Solenoid Valve 1
LLSV1
190
OFF =
Liquid line solenoid valve (Compressor 1) closed.
ON =
Liquid line solenoid valve (Compressor 1) open.
Liquid Line Solenoid Valve 2
LLSV2
191
OFF =
Liquid line solenoid valve (Compressor 2) closed.
ON =
Liquid line solenoid valve (Compressor 2) open.
Liquid Line Solenoid Valve 3
LLSV3
192
OFF =
Liquid line solenoid valve (Compressor 3) closed.
ON =
Liquid line solenoid valve (Compressor 3) open.
Liquid Line Solenoid Valve 4
LLSV4
193
OFF =
Liquid line solenoid valve (Compressor 4) closed.
ON =
Liquid line solenoid valve (Compressor 4) open.
Fan Output
FAN
194
OFF =
Fan off.
ON =
Fan on.
Heating Stage 1
HEAT1
196
OFF =
Heating stage 1 off.
ON =
Heating stage 1 on.
Heating Stage 2
HEAT2
197
OFF =
Heating stage 2 off.
ON =
Heating stage 2 on.
Heating Stage 3
HEAT3
198
OFF =
Heating stage 3 off.
ON =
Heating stage 3 on.
Heating Stage 4
HEAT4
199
OFF =
Heating stage 4 off.
ON =
Heating stage 4 on.
Heating Stage 5
HEAT5
200
OFF =
Heating stage 5 off.
ON =
Heating stage 5 on.
Heating Stage 6
HEAT6
201
OFF =
Heating stage 6 off.
ON =
Heating stage 6 on.
Alarm Output
ALARM
202
OFF =
No alarm present or silenced through alarm silence
input on S7600.
ON =
Alarm present. Turn on annunciation.
Supply Motor Open
SUPLY+
203
OFF =
No action.
(Floating Output)
1
ON =
Drive vanes open to increase air volume.
Содержание PM7600B