Galaxy 3 Series Programming Manual
58
17 = Restart
This parameter re-configures the system without the need to remove and reconnect the power. The system
displays a
WARNING!!! ent=RESET SYSTEM
, press the
ent
key to reconfigure the system. The keypad
display becomes blank for a few seconds, then displays the message
Configuring Please Wait
. When
configuration is complete the banner returns to the normal display (day mode). The
Restart
option configures
any modules that have been added to the system but gives an alarm if there are any tampers open or if any
modules are reported as missing.
NOTE:
This parameter exits engineer mode. It is however recommended that the exit engineer mode se-
quence is used when adding or removing modules from the system.
NOTE:
Outputs are momentarily reset during the restart. If the system has a communications requirement,
put it on test before using the restart.
18 = Stop Set
This parameter, when set to
1
(enabled), prevents the system from set override if there is a communication or
power fail condition at the time of starting the setting procedure. If the condition is the result of an open
Line
Fail
or
AC Fail
zone, then the system can not be set until the zone is closed or omitted. The
Stop Set
param-
eter is set to
0
(disabled) by default.
NOTE: Battery Low
will also prevent the system from setting.
19 = Part Alarm
When the
Part Alarm
parameter is set to
1
(enabled — default setting) the
Bells
and
Strobe
outputs activate
if an alarm condition occurs when the system is part set.
When the
Part Alarm
parameter is set to
0
(disabled) the
Bells
and
Strobe
outputs are disabled when the
system is part set.
NOTE:
The
Horn, Entry/Exit
and
Intruder
outputs are not affected by this parameter.
This parameter can be assigned a different value for each group.
20 = Power Delay
This parameter determines the delay between the activation of
AC Fail
outputs following a mains failure to
allow the power to return before signalling the fault. The
Power Delay
is programmable within the range
0–50
minutes; the default is
10
.
This parameter can be assigned a different value for each group.
21 = Reset MGR
This parameter should only be used if the Master Manager code is lost or must be replaced. On selecting the
Reset MGR
parameter, a warning message is displayed:
WARNING!!! ENT=Code Change
; press the
ent
key to erase current code and reset it to the default of
12345
.
51 - Parameters (cont’d)
Содержание 3-144
Страница 1: ...Honeywell Security Galaxy 3 48C 3 144 3 144C 3 520 3 520C Programming Manual ...
Страница 2: ......
Страница 8: ...Galaxy 3 Series Programming Manual 2 ...
Страница 30: ...Galaxy 3 Series Programming Manual 24 ...
Страница 184: ...Galaxy 3 Series Programming Manual 178 ...
Страница 188: ...Galaxy 3 Series Programming Manual A 4 ...
Страница 202: ...Galaxy 3 Series Programming Manual C 2 ...
Страница 212: ...2 Galaxy 3 Series Programming Manual ...
Страница 213: ...3 Galaxy 3 Series Programming Manual ...