Galaxy 3 Series Programming Manual
D-1
Appendix D: Event Log Messages
Event Log
NOTE:
M = Mandatory. NM = Non-Mandatory
NOTE:
A plus (+) means an event has started. A negative (-) means an event has finished.
KEYPAD TEXT
DESCRIPTION
Trigger Event
0001 + CU-BATT
Control Unit Standby Battery Low has occurred (battery voltage below 10.5 Vd.c.).
13. Elec Status
20. Fault
M
0001 - CU-BATT
Control Unit Standby Battery Low has finished (battery voltage now above 10.5 Vd.c.).
13. Elec. Status
M
0002 + CU-AC
Control Unit Mains (a.c.) Power Fail has occurred.
13. Elec. Status
20. Fault
M
0002 - CU-AC
Control Unit Mains (a.c.) Power Fail has finished.
13. Elec. Status
M
0003 + LID TAMP
Lid Tamper on control unit has occurred.
9. Tamper
M
0003 - LID TAMP
Lid Tamper on control unit has finished.
9. Tamper
18. Zone restoral
M
0004 + AUX TAMP
Auxiliary Tamper on control unit has occurred.
9. Tamper
M
0004 - AUX TAMP
Auxiliary Tamper on control unit has finished.
9. Tamper
18. Zone restoral
M
ABORT SET+
Setting process aborted
11. Reset
NM
+AC+BATT
AC Fail and battery voltage low.
13. Elec. Status
20. Fault
M
+ AC FAIL
AC Fail zone activated (opened) or an AC Fail on a Power Supply Unit.
13. Elec. Status
20. Fault
M
– AC FAIL
AC Fail zone de-activated (closed) or an AC Fail on a Power Supply Unit has
stopped.
13. Elec. status
20. Fault
M
ALARM EXT+
Alarm extend zone activated.
3. 24 Hours
16. Log Zone
M
ALM CAUSE
Reset of system required by entry of an alarm cause code.
Always TR
M
ADDED
Engineer has added a module to the system.
9. Tamper
M
ARC TEST
Alarm Receiving Centre Test
Always TR
NM
ATM-1+
ATM-1 zone activated.
3. 24 Hours
16. Log Zone
NM
ATM-2+
ATM-2 zone activated.
3. 24 Hours
16. Log Zone
NM
ATM-3+
ATM-3 zone activated.
3. 24 Hours
16. Log Zone
NM
ATM-4+
ATM-4 zone activated.
3. 24 Hours
16. Log Zone
NM
AUTOTEST
Automatic Test of the system via a comms module
Always TR
AUT
Autoset timer activated.
None
NM
AUTOTIMER –
Autoset timer de-activated.
None
NM
BURG HIGH
High priority intruder alarm zone open
2. Intrude
18. Zone Restoral
M
BURG LOW
Low priority intruder alarm zone open
2. Intrude
18. Zone Restoral
M
+BAT FUSE
Battery fuse on Power Supply Unit blown
13. Elec Status
20. Fault
M
+ BATT LOW
Battery Low activated on Power Supply Unit.
13. Elec. status
20. Fault
M
– BATT LOW
Battery Low de-activated on Power Supply Unit.
13. Elec. status
20. Fault
M
BEAM PAIR+
Beam Pair zones activated (opened).
2. Intruder
NM
BEGIN SET+
Setting process started
None
NM
+ BELL FAIL
Bell Fail zone opened
16. Log Zone
NM
+ BELL TAMP
Bell Tamper zone activated (opened).
9. Tamper
M
– BELL TAMP
Bell Tamper zone de-activated (closed).
9. Tamper
18. Zone restoral
M
CANCEL
Alarm activation Cancelled by a valid user Code (system or Group(s) still Set).
11. Reset/Cancel
NM
COMM FAIL
Communication Failure has occurred on a comms module.
20. Fault
M
CONFIRM
Two independent alarms
2. Intruder
M
COPY SITE
Remote Copy of the Site (system) has occurred via Galaxy Gold or the RS232 Module. None
NM
CUSTOM-A
Custom-A zone activated (opened).
5. Custom zones
16. Log Zone
NM
CUSTOM-B
Custom-B zone activated (opened).
5. Custom Zones
16. Log Zone
NM
CU-FUSE +
Control Unit Fuse trouble
9. Tamper
13. Elec Status
20. Fault
M
DELAY ALM
PA Delay Alarm zone activated after PA Delay timeout.
1. PA/duress
M
DL/SL ALM
PA Delayed Silent zone activated after PA Delay timeout.
1. PA/duress
M
DOOR PROP
MAX - Door left open
4. Security
NM
DR MASKED
Detector masked. Activity monitoring of zone has failed.
15. Trouble
20. Fault
M
DUAL
Dual (Double Knock) zone activated (opened).
2. Intruder
M
Содержание 3-144
Страница 1: ...Honeywell Security Galaxy 3 48C 3 144 3 144C 3 520 3 520C Programming Manual ...
Страница 2: ......
Страница 8: ...Galaxy 3 Series Programming Manual 2 ...
Страница 30: ...Galaxy 3 Series Programming Manual 24 ...
Страница 184: ...Galaxy 3 Series Programming Manual 178 ...
Страница 188: ...Galaxy 3 Series Programming Manual A 4 ...
Страница 202: ...Galaxy 3 Series Programming Manual C 2 ...
Страница 212: ...2 Galaxy 3 Series Programming Manual ...
Страница 213: ...3 Galaxy 3 Series Programming Manual ...