Galaxy 3 Series Programming Manual
98
33 Warning (Latch)
The
Warning
output is activated by the first occurrence of a high (1200-1300
Ω
) and low (800-900
Ω
)
resistance reading on each of the system zones in a single 24 hour period: the activating zone is recorded in the
log.
NOTE:
The time period finishes at midnight, not 24 hours from first activation.
Subsequent high and low resistance readings from the same zone on the same day do not activate the output if
it has been reset by a valid user code.
NOTE:
If a low resistance reading is followed by a high resistance reading, the
Warning
output activates on
the first occurrence of both activations.
34 Custom A (Latch)
The
Custom-A
output is activated whenever a
Custom-A
zone is activated.
35 Custom B (Latch)
The
Custom –B
output is activated whenever a
Custom-B
zone is activated.
36 Test (Pulse)
The
Test
output is activated at 12:00 hours each day for two seconds – the period of the
Pulse
can be
altered. This output can be used to perform a daily test on a digicom connected to the system.
37 Reset RQD (Latch)
The
Reset RQD
output is activated when a system, tamper or PA alarm has occurred that requires to be
reset by the engineer (type 3.7) code. Refer to option
51=PARAMETERS
for details modifying the code
types assigned to the
06=System Reset, 07=Tamper Reset
and
22=PA Reset
parameters.
38 Mask (Latch)
The
Mask
output is activated whenever the zone resistance values returned by the RIO to the panel fall within
the range of the masked state (see Parameter 51.46, Zone Resistance). The output is not subject to the
Rearm
parameter: It latches on and remains active until a valid group code (type 2 or above) is entered.
39 Valid Code (Reflex)
The
Valid Code
output is activated by the entry of any valid code. If the
Output Mode
assigned is
Reflex
,
the output remains active while the user is accessing the menu and setting and unsetting the system. Once the
menu is exited or the system sets or unsets, the output is restored.
40 Fail Set (Latch)
The
Fail Set
is activated if the system (or assigned groups) fails to set within the time assigned in parameter
35=Fail to Set –
refer to option
51=PARAMETERS
.
41 Duress (Latch)
The
Duress
function is activated on entry of a
Duress Code
(any valid code followed by two #’s, or a code
assigned as a
Duress Code
using menu option
42 – Codes
). The output is not subject to the
Rearm
param-
eter: it latches on and remains active until a valid code (type 2 or above) is entered.
53 - Program Outputs (cont’d)
Содержание 3-144
Страница 1: ...Honeywell Security Galaxy 3 48C 3 144 3 144C 3 520 3 520C Programming Manual ...
Страница 2: ......
Страница 8: ...Galaxy 3 Series Programming Manual 2 ...
Страница 30: ...Galaxy 3 Series Programming Manual 24 ...
Страница 184: ...Galaxy 3 Series Programming Manual 178 ...
Страница 188: ...Galaxy 3 Series Programming Manual A 4 ...
Страница 202: ...Galaxy 3 Series Programming Manual C 2 ...
Страница 212: ...2 Galaxy 3 Series Programming Manual ...
Страница 213: ...3 Galaxy 3 Series Programming Manual ...