Galaxy 3 Series Programming Manual
59
22 = PA Reset
This option allows the engineer or the remote code to determine the code type that can reset the system
following a PA activation. The default type is
3.6
— manager; the programmable range is:
•
2.3 - 2.5
for the user
•
3.6
for the manager
•
3.7
for the engineer
This parameter can be assigned a different value for each group.
The panel only requests Engineer Level Reset if alarms have been signalled, via the Communication Module
and appropriate type reset is set to 3.7. If no signal is transmitted, the reset will automatically be reduced to
type 3.6. This feature is only active when the DTMF signalling format is selected.
23 = Print Codes
The
Print Codes
option, when set to
1
(enabled), allows the manager to print a list of the PINS for each of
the users. The option defaults to
0
(disabled).
24 = Exit Alarm
If the
Exit Alarm
parameter is set to
1
(enabled), any zone other than
Final
,
Exit
,
Entry
or
Push-Set
(or
Secure Final
or
Part Final
when acting as a
Final
) that is opened during the exit time causes a full alarm
condition to be activated. The default is
0
(disabled).
NOTE:
This option must be used only when specified.
This parameter can be assigned a different value for each group.
If the
Exit Alarm
parameter is enabled, any zone that is open when the Autoset begins (at the end of the pre-
warning period) causes an immediate full alarm condition to be activated.
If the
Exit Alarm
parameter is disabled, any zone open when the Autoset begins (at the end of the pre-
warning period) results in an “urgent” bleeping from the
Entry/Exit Horns
. If the open zones are not closed
by the end the time assigned in parameter
35 = Fail To Set
, a full alarm is activated along with any outputs
programmed as
Fail-Set
.
25 = Global Copy
The
Global Copy
parameter changes all zones within the selected range to the function of the first zone in the
range. On selection of the parameter, a warning message is displayed indicating that the zone functions will be
altered —
WARNING!!! ENT=ZONE CHANGES
: press the
ent
key to continue or the
esc
key to abort
the programming. The address and function of the first zone on the system are displayed:
•
Copy Start:
Use the
A
or
B
key to select the first zone in the range to be copied and press the
ent
key.
The function of this zone will be copied to all subsequent zones in the range;
•
Copy End:
Use the
A
key to move to the last zone in the range to be copied.
•
Press the
ent
key to copy the zone function to the selected range.
51 - Parameters (cont’d)
Содержание 3-144
Страница 1: ...Honeywell Security Galaxy 3 48C 3 144 3 144C 3 520 3 520C Programming Manual ...
Страница 2: ......
Страница 8: ...Galaxy 3 Series Programming Manual 2 ...
Страница 30: ...Galaxy 3 Series Programming Manual 24 ...
Страница 184: ...Galaxy 3 Series Programming Manual 178 ...
Страница 188: ...Galaxy 3 Series Programming Manual A 4 ...
Страница 202: ...Galaxy 3 Series Programming Manual C 2 ...
Страница 212: ...2 Galaxy 3 Series Programming Manual ...
Страница 213: ...3 Galaxy 3 Series Programming Manual ...