Galaxy 3 Series Programming Manual
81
24 Line Fail
The
Line Fail
function is used to monitor the communication line that a remote signalling device is connected
to for communications failure.
When the system is in the unset state, the first activation of a
Line Fail
zone causes a local alarm and the
message
COMMS FAILURE
is displayed, subsequent
Line Fail
activations do not sound the local alarm;
the only indication is the keypad display.
When the system is set, activation of the
Line Fail
zone overrides the
Bell Delay
parameter; on unsetting the
system a local alarm is generated and the keypad gives an indication that
Line Fail
zone has activated. If an
alarm condition occurs while the
Line Fail
is active, an instant full alarm is generated.
If the
Line Fail
zone is active at the point of setting, a warning message is displayed; the user can choose to
continue or abort the setting procedure. It is also possible to prevent the system setting if the
Line Fail
is
active by enabling the
Stop Set
parameter (option
51.18
).
25 AC Fail
This function is used to monitor a remote power supply. In the event of a power failure the
AC Fail
zone is
activated; the activation (
+
) and de-activation (–) of the zone is recorded in the event log.
26 Log
This zone type has no operational function; it is designed to record the activation of a zone in both the set and
unset state. The activation (
+
) and de-activation (–) of
Log
zones is recorded in the event log.
27 Remote Access
This function is used to disable remote servicing of the Galaxy panel. When the
Remote Access
zone is
active the Galaxy Gold software is prevented from gaining access to the Galaxy panel.
28 Video
This function is identical to the
Intruder
function, with the exception that the cumulative number of activations
from
Video
zones, before a full alarm is generated, is programmable. The number of activations required is
determined by the
Video
parameter (option
51.30
); the range is
1–9
. The activation count is incremented
when any
Video
zone in the group activates; the count is reset to zero when the group is unset.
29 Video Exit
The
Video Exit
function is identical to the
Video
function, with the exception that the user can activate the
zone during setting and unsetting without incrementing the
Video
activations count. The
Video
output is not
activated during setting and unsetting.
52 - Program Zones (cont’d)
Содержание 3-144
Страница 1: ...Honeywell Security Galaxy 3 48C 3 144 3 144C 3 520 3 520C Programming Manual ...
Страница 2: ......
Страница 8: ...Galaxy 3 Series Programming Manual 2 ...
Страница 30: ...Galaxy 3 Series Programming Manual 24 ...
Страница 184: ...Galaxy 3 Series Programming Manual 178 ...
Страница 188: ...Galaxy 3 Series Programming Manual A 4 ...
Страница 202: ...Galaxy 3 Series Programming Manual C 2 ...
Страница 212: ...2 Galaxy 3 Series Programming Manual ...
Страница 213: ...3 Galaxy 3 Series Programming Manual ...