PW3390 Power Analyzer Communication Command Instruction Manual Second Edition
79/107
Set and Query SUM’s Normal Measurement Value Communication Output Items
Syntax
Command
:MEASure:ITEM:SUM <Udata>,<Idata>,<Pdata>,<Sdata>,
<Qdata>,<PFdata>,<DEGdata>
Query
:MEASure:ITEM:SUM?
Response
<Udata>,<Idata>,<Pdata>,<Sdata>,<Qdata>,<PFdata>,<DEGdata>
128
64
32
16
8
4
2
1
bit 7
bit 6
bit 5
bit 4
bit 3
bit 2
bit 1
bit 0
Udata
-
-
-
-
-
U123
U34
U12
Idata
-
-
-
-
-
I123
I34
I12
Pdata
-
-
-
-
-
P123
P34
P12
Sdata
-
-
-
-
-
S123
S34
S12
Qdata
-
-
-
-
-
Q123
Q34
Q12
PFdata
-
-
-
-
-
PF123
PF34
PF12
DEGdata
-
-
-
-
-
DEG123 DEG34 DEG12
Description
Command
Sets the normal measurement value communication output
items of SUM as
– 255.
Query
Returns the normal measurement value communication output items of SUM
as numerical value.
Example
Command
:MEAS:ITEM:SUM 0,0,1,1,0,1,0
Set the effective power, apparent power and power factor data of SUM12 to
ON.
Query
:MEAS:ITEM:SUM?
Response
:MEASURE:ITEM:SUM 0,0,1,1,0,1,0 (WHEN HEADER IS ON)
0,0,1,1,0,1,0 (WHEN HEADER IS OFF)
Note
To specify individually saved items in the Udata and Idata and specify the unbalance ratio,
use :MEASure:ITEM:U, :MEASure:ITEM:I Command after this command is executed.
During Query, if even 1 item of each of the channel is turned to ON, the channel will become
ON.
Some items are unselectable due to the wiring and integration mode.
When an unselectable item is specified, an execution error will occur and other items will also
not be set.
Содержание PW3390
Страница 108: ......