When ATevo is in EQUALIZE mode, the charger will:
• Ramp up to the EQUALIZE VOLTAGE set point.
• Start the EQUALIZE TIMER.
• Alternate display between showing the HOME screen and a screen that shows the
EQUALIZE TIME REMAINING.
ATevo will remain in EQUALIZE mode until either the EQUALIZE TIMER expires or the charge
mode is manually switched back to FLOAT.
Last modified: 11 February 2021
7.1.3.
7.1.3. Changing Equalize Method
Changing Equalize Method
The EQUALIZE METHOD button switches the equalize method between MANUAL TIMER and
AUTOMATIC TIMER. The present equalize method is displayed at the top right of the HOME
screen ‘
Eqlz Mthd: Man
’ specifies MANUAL TIMER and ‘
Eqlz Mthd: Auto
’ specifies AUTOMATIC
The CHARGE MODE button is in the same relative location as the CHGR MODE
button on legacy ATevo chargers. Its functionality is equivalent in that it changes
charge mode between EQUALIZE and FLOAT.
*
https://www.youtube.com/embed//H8zGOGu_EyE?rel=0&start=8
HindlePower Inc
ATevo Operations–Single Phase Input–Group II (30-100 Adc Output) - 1_en
Copyright HindlePower Inc. 2021
Page 71 of 171