I/O Connections (Style-5070)
I/O Connections (Style-5070)
1. Use a dc disconnect switch or circuit breaker between ATevo and the dc bus. This
device should have lockout capability to allow ATevo to be disconnected from the dc
bus for maintenance.
2. Remove safety shield per
Removing Protective Safety Shield in Section 4
.
3. Run dc wiring into ATevo, ending at right side of I/O panel.
4. Connect wires to appropriate dc output CU-AL compression lugs on right side of I/O
panel.
5. Using a flat-blade screwdriver, securely tighten lugs for pos(+) and neg(-)
connections.
6. Check all dc output connections, and reinstall safety shield.
To prevent equipment damage, confirm polarity of pos(+) and neg(-) wiring.
!