9.7.
9.7. Battery Open Test
Battery Open Test
The Battery Open Test feature will detect if the connection between the battery and ATevo has
been lost, or if there is a weak or faulty battery. The test lowers the charger voltage and
verifies whether the battery can assume the present dc load. This test can be run manually or
according to a set schedule.
The Battery Open Test will fail if the dc bus drops below a configurable voltage set point. When
such occurs the test aborts immediately and ATevo will raise output voltage back to the present
Float or Equalize setting. Test duration is configurable as seen below.
If the test fails, a Battery Open alarm is generated and can only be cleared by the Unlatch
Battery Open Alarm control.
Last modified: 1 March 2021
9.7.1.
9.7.1. Battery Open Test Settings
Battery Open Test Settings
To access and configure Battery Open Test settings:
MENU > TESTING > ‘Test Settings’
To configure test duration:
‘Run test for up to:’ > adjust duration
HindlePower Inc
ATevo Operations–Single Phase Input–Group II (30-100 Adc Output) - 1_en