Configuring ATevo for Forced Load Sharing
Configuring ATevo for Forced Load Sharing
You must assign a charger ID to each ATevo connected in forced load sharing. Configure one as
the Primary and all other chargers as Secondary chargers.
To configure an ATevo for Forced Load Sharing:
MENU > COMMUNICATION > Port ‘X’ setup
• ‘X’ is either ‘2’ or ‘3’ for Port 2 or Port 3. The Port configured for forced load share must
be the port that the Serial Communications Adapter is plugged into that is wired to the
Forced Load Sharing network.
• Select ‘loadshare P’ for the Primary ATevo, or ‘loadshare S’ for Secondary ATevos.
Press the EDIT/ENTER button to accept the new selection. The charger ID may now be changed.
Press the ESC button to return to the previous screen. If a port setting was changed, the ATevo
will prompt to RESET. Select YES to RESET the ATevo. The new port settings will not become