• Remove the two (2) screws that connect the Transformer (T1) primary wire lugs to the
MOV Board (A9).
• Remove the bolt that mounts the MOV Board (A9) to the breaker bracket.
• Bolt the new MOV Board (A9) onto the breaker bracket.
• Install the two (2) screws through the lugs that connect MOV Board to the primary wires
and tighten nuts.
• Replace the safety shield and close the front panel door.
• Restart the ATevo.
Last modified: 4 March 2021
16.3.8.
16.3.8. Replacing Eliminator Filter
Replacing Eliminator Filter
Capacitor – optional
Capacitor – optional
For 30 Adc, 40 Adc and 50 Adc ATevos
For 30 Adc, 40 Adc and 50 Adc ATevos
The C2 filter consists of a single capacitor with two wires that connect to the Power Board.
Preparation:
Preparation:
• Shut down and lock out all power to ATevo.
• Remove safety shield.
• Locate C2 capacitor mounted to back panel near top left of the enclosure.
Removal of Existing Capacitor (C2x) Assembly:
Removal of Existing Capacitor (C2x) Assembly:
• Loosen screw on capacitor bracket at bottom of capacitor mounting and disconnect wires
attached to capacitor from Power Board. Replacement C2 will have new wires with pre-
crimped terminals.
• Remove C2 capacitor.
The pos(+) and neg(-) wires have different terminals to eliminate the
possibility of connecting in reverse polarity.
Installation of New C2 Capacitor Assembly:
Installation of New C2 Capacitor Assembly:
• Connect wires of new C2 capacitor assembly to Power Board.
• Insert new C2 into capacitor bracket and tighten screw at base of capacitor.
• Replace safety shield, close door and restart ATevo.
For 75 Adc and 100 Adc ATevos
For 75 Adc and 100 Adc ATevos
The C2 filter is mounted next to the C1 filter capacitor(s) and connects to the C1 capacitor with
a bus bar. Follow instructions in
for replacing both C1 and C2.