Enabling Remote Sense
Enabling Remote Sense
To have ATevo regulate dc output to the voltage present at the Remote Sense leads, move both
the Remote Sense SHORTING BLOCKs (JP103 and JP104) to the REMOTE SENSE side of the pin
headers. The SHORTING BLOCKS should be installed on the two (2) pins closest to the edge of
the board.
Enabling Local Sense
Enabling Local Sense
Local Sense is the factory default configuration. Unless otherwise specified, all ATevos are
shipped configured to use local sense. In this configuration, ATevo regulates dc output to the
voltage present at the charger output terminals (CB2+/-).
Jumper configuration will have both Remote Sense SHORTING BLOCKs (JP103 and JP104) at the
LOCAL SENSE side of the pin headers. SHORTING BLOCKS will be installed on the two (2) pins
farthest from the edge of the board.
Last modified: 5 May 2021
13.4.
13.4. Disabling Remote Sense
Disabling Remote Sense
If you need to temporarily disable Remote Sense:
• De-energize and lock out all ac and dc voltages within the ATevo enclosure.
• Check with a voltmeter.
• Remove the safety shield.
• Move SHORTING BLOCKs to Local Sense configuration per
• Replace safety shield and close front panel door.
• Re-energize ATevo.
If Remote Sense is to be disabled for extended periods of time or permanently
disabled, it is highly recommended that the sense leads (the twisted pair cable)
be disconnected from both the battery and terminal block (A2-TB1).
*