Notes
Notes
• Maximum current is 150mA.
• Run the twisted-pair cable with the sense leads in a dedicated conduit.
• Fuse each of the sense wires.
Last modified: 5 March 2021
13.3.
13.3. Configuring Remote Sense
Configuring Remote Sense
Jumpers
Jumpers
ATevo must be configured to sense dc output voltage used for regulation at either the charger’s
dc output or at the voltage present on the Remote Sense terminal block (A2-TB1). This
configuration is accomplished by moving shorting block jumpers located on ATevo’s Power
Board (A2).
Locating Remote Sense Configuration Jumpers
Locating Remote Sense Configuration Jumpers
Remote Sense Configuration Jumpers (JP103 and JP104) are located on the Power Board next to
the Remote Sense terminal block (A2- TB1). Each jumper consists of a 3-pin header and a
SHORTING BLOCK that shorts (or connects) two (2) pins of the header together.