USE ONLY HAYWARD GENUINE REPLACEMENT PARTS
30 minutes and the filter pump will turn off while the valves are turning. The chlorinator will not operate if freeze protection is the only
reason the pump is running.
If Yes is selected:
Freeze Protect Temperature?
Select the temperature to be used for freeze protection. Temperature is adjustable from
33ºF-42ºF (1ºC-6ºC). 38ºF (3ºC) is default. This threshold will be used for all outputs that have freeze protection enabled.
Freeze Protect Speed?
This is the speed of the pump while freeze protection is active. Select the desired pump speed %.
How many Heaters?
This question is for THIS BODY OF WATER ONLY. For example: If you have 2 heaters, one for the pool Body of Water and one for the
spa Body of Water, you would answer “1” to this question.
If “1”or more is selected:
Heater Cooldown Enabled?
This feature ensures that the heater cools down before water circulation is stopped. When enabled, the OmniPL
will continue to run the filter pump for 5 minutes after the heater turns off.
Heater Extend Enabled?
If “Enabled”, the filter extend logic keeps the filter pump running beyond the normal turn-off time until the pool (or
spa) is heated up to the desired temperature setting. Heater extend will NOT cause the filter pump to turn on, it will only delay the turn off time
when the heater is operating.
Maximum Settable Temperature?
This is the maximum allowed setting for the heater regardless of its default range. There may be circum-
stances where you will want to limit the high temperature of your heater to a temperature that is lower than the factory high setting.
Select and Configure a Heater
At this screen, you can add, delete and configure your heater(s). Select the desired heater, then touch the
Advance button. When finished configuring heater(s), you’ll be returned to this same screen. Touch the Done button and advance to the next
section of configuration. Refer to the following information when configuring heater(s):
What Type?
Heater choices are Solar, Heat Pump and Gas. Make your selection and advance.
If Gas Heater is selected:
Name Heater
Select the box, then type the desired name for your heater. This name will be used when referring to this particular
heater.
Which Relay is it Wired to?
Selecting the box will bring you to a table showing all detected relays. Select the low voltage relay that
is wired to the heater (refer to the Connection Table for this information), then advance. The relay should now be shown in the box.
Advance to the next screen to continue gas heater configuration.
If more than one heater has been configured for this Body of Water:
Heater Priority Level?
Because more than one heater is configured to heat this Body of Water, you can set the Priority for
which heater you’d like to use first (selection “1”). If the priority heater can’t meet the demand, the next heater will start
(selection “2”).
Heater Priority Duration?
Set the amount of time that you will allow the priority heater (“1”) to heat before allowing the next
heater to start. If the priority heater meets the demand within this time frame, the next heater will not be used. Note that a
time interval setting of “0” will eliminate priority and always run both heaters at the same time.
Minimum Operation Speed?
For variable speed pumps, select the lowest pump speed that is allowed while heating. Set a speed
that will ensure that there will be sufficient flow for the heater to operate properly.
If Heat Pump is selected:
Name Heater
Select the box, then type the desired name for your heater. This name will be used when referring to this particular
heater.
Which Relay is it Wired to?
Selecting the box will bring you to a table showing all detected relays. Select the low voltage relay that
is wired to the heater (refer to the Connection Table for this information), then advance. The relay should now be shown in the box.
Advance to the next screen to continue heat pump configuration.
Minimum Allowed Air Temperature for Heater?
If the air temperature falls below this setting, the heater will be prevented from
running, regardless of conditions. This feature is especially useful for heat pumps which become less efficient as the outdoor ambient
temperature falls.
If more than one heater has been configured for this Body of Water:
Heater Priority Level?
Because more than one heater is configured to heat this Body of Water, you can set the Priority for
which heater you’d like to use first (selection “1”). If the priority heater can’t meet the demand, the next heater will start
(selection “2”).