10/6/10
888-2629-200
2-51
WARNING: Disconnect primary power prior to servicing.
Section 2 Installation
Maxiva ULX COFDM Series
2.14.1 Setting the Transmitter Flow Rate
STEP 1
Check the transmitter flow rate.
Press SYSTEM>SYSTEM
COOLING>COOLING METERS. The first line shows the transmitter
flow rate.
STEP 2
Adjust the Flow Rate if necessary.
Adjust the inlet valve for the
transmitter cabinet until the flow rate indicated on the GUI matches the
nominal flow rate of the transmitter model as shown in the table below
or as indicated in the Liquid Cooling System Layout drawing
NOTE:
Actual flow rate may deviate from nominal depending on site specifics like pipe
diameter, number of elbows, and run length. The flow rate must be above the trip
point level in order to prevent frequent faults and pump switches. Refer to the
Outline drawing and Plumbing layout drawing for more details.
Table 2-11 Cooling System Flow Rates
MODEL
NOMINAL TRANSMITTER FLOW RATE
Trip Point
(LPM)
PA Modules
ULX-1100**
38 liters per minute
15
2
ULX-1700**
45 liters per minute
19
3
ULX-2300**
53 liters per minute
23
4
ULX-3400**
65 liters per minute
30
6
ULX-4400**
76 liters per minute
38
8
ULX-5500**
99 liters per minute
46
10
ULX-6500**
121.0 liters per minute
53
12
ULX-8700**
129.0 liters per minute
70
16
ULX-9500**
121.0 liters per minute - for 12 PA cabinet
65 liters per minute - for 6 PA cabinet
53
30
(12+6)
ULX-12600**
121.0 liters per minute - for each cabinet
53
(12+12)
ULX-17400**
129.0 liters per minute - for each cabinet
70
(16+16)
ULX-1890**
121.0 liters per minute - for each cabinet
53
(12+12+12)
ULX-26100**
129.0 liters per minute - for each cabinet
70
(16+16+16)
Содержание Maxiva ULX
Страница 2: ...ii 888 2629 200 10 6 10 WARNING Disconnect primary power prior to servicing ...
Страница 4: ...iv 888 2629 200 10 6 10 WARNING Disconnect primary power prior to servicing ...
Страница 6: ...MRH 2 888 2629 200 10 6 10 WARNING Disconnect primary power prior to servicing ...
Страница 8: ...viii 888 2629 200 10 6 10 WARNING Disconnect primary power prior to servicing ...
Страница 9: ...10 6 10 888 2629 200 ix WARNING Disconnect primary power prior to servicing ...
Страница 10: ...x 888 2629 200 10 6 10 WARNING Disconnect primary power prior to servicing ...
Страница 12: ...xii 888 2629 200 10 6 10 WARNING Disconnect primary power prior to servicing ...
Страница 14: ...xiv 888 2629 200 10 6 10 WARNING Disconnect primary power prior to servicing ...
Страница 18: ...Table of Contents Continued 4 ...
Страница 296: ...B 20 888 2629 200 10 6 10 WARNING Disconnect primary power prior to servicing Maxiva ULX COFDM Series ...