WARNING: Disconnect primary power prior to servicing.
Section 1 Introduction
Maxiva ULX COFDM Series
Figure 1-9 Cooling System Control Panel
The cooling system control panel shown in Figure 1-9 has local controls on the front
which allow manual selection of:
a.
ISOLATOR ON/OFF
b.
HEAT EXCHANGER FANS - Manual, OFF, or Remote
c.
PUMP SELECT - A or B pump is selected when pressed
d.
TEMP CONTROLLER - Sets fan cycle temps. Factory settings are Fan 1 set
point will be set at 32 C with a 5 degree hysteresis window. This means Fan 1
turns ON at 34.5 C and shuts off at 29.5 C. Fan 2 set point will be set at 37.5 C
also with a 5 degree hysteresis window. This means Fan 2 turns ON at 40 C and
shuts off at 35 C.
e.
SYSTEM CONTROL - LOCAL/REMOTE - Allows local control or remote con-
trol via transmitter.
f.
HEAT EXCHANGER TEMP CONTROL - PID controller used to set fan ON and
OFF temperatures.
The control panel also has the following status indicators:
g.
PUMP - A RUN (ON = Green)
AC Isolator ON/OFF
P
A
B
Pump A or B
Pump A or B
Run LEDs
FAN A or B
Run LEDs
p
Selected LEDs
Run LEDs
Pump
Select
Controller
Set Temp. Set Point
& Hyserisis
Select
System Control
LOCAL/OFF/REMOTE
& Hyserisis
Screwdriver Lock
Pump Isolators
ON/OFF
Содержание Maxiva ULX
Страница 2: ...ii 888 2629 200 10 6 10 WARNING Disconnect primary power prior to servicing ...
Страница 4: ...iv 888 2629 200 10 6 10 WARNING Disconnect primary power prior to servicing ...
Страница 6: ...MRH 2 888 2629 200 10 6 10 WARNING Disconnect primary power prior to servicing ...
Страница 8: ...viii 888 2629 200 10 6 10 WARNING Disconnect primary power prior to servicing ...
Страница 9: ...10 6 10 888 2629 200 ix WARNING Disconnect primary power prior to servicing ...
Страница 10: ...x 888 2629 200 10 6 10 WARNING Disconnect primary power prior to servicing ...
Страница 12: ...xii 888 2629 200 10 6 10 WARNING Disconnect primary power prior to servicing ...
Страница 14: ...xiv 888 2629 200 10 6 10 WARNING Disconnect primary power prior to servicing ...
Страница 18: ...Table of Contents Continued 4 ...
Страница 296: ...B 20 888 2629 200 10 6 10 WARNING Disconnect primary power prior to servicing Maxiva ULX COFDM Series ...