10/6/10
888-2629-200
2-41
WARNING: Disconnect primary power prior to servicing.
Section 2 Installation
Maxiva ULX COFDM Series
box. Improper fan rotation can be corrected by changing any two of the
phases (inside the control panel) supplying the fan.
2.11.2 Initial System Leak Tests
During the leak tests in the following steps, check the static pressure of the cooling
system while the pumps are momentarily deenergized. During pump operation the static
pressure of the system will drop as the air purger and automatic air vents bleed trapped
air from the system. With the pumps deenergized, the cooling system must be charged
with coolant to a pressure of 10 psig. This is accomplished by attaching the charge
pump to a low point in the system or to the charge point (see Figure 2-1) in the pump
module assembly and pumping in additional water until the static pressure again
reaches 10 psig
NOTE:
System flow can be monitored by viewing the sight tube which is located atop the
system air purger. Low coolant level or the presence of bubbles in the sight tube
indicates air in the system and a need for recharging the system with additional
coolant.
STEP 1
Turn on pump A for several minutes.
Upon the establishment of a
steady (no air bursts) volume of water throughout the system, begin
visual check for leaks. Turn off Pump A after thorough leak checks.
STEP 2
Turn on pump B for several minutes.
Upon the establishment of a
steady (no air bursts) volume of water throughout the system, continue
visual check for leaks. Turn off Pump B after thorough leak checks.
NOTE:
If flow is insufficient, the flow switch will activate and turn the pumps off for
protection
STEP 3
Check immediately for any leaks at the following cooling system
points
.
•
Transmitter inlet and outlet pipe connections
•
Pump module inlet and outlet pipe connections
•
Heat exchanger inlet and outlet pipe connections
•
All solder joints, system valves and drain valves
STEP 4
Repair any detected leaks.
If leaks have developed, depending upon
the given leak’s location, water may have to be drained from the system
before making repairs.
Содержание Maxiva ULX
Страница 2: ...ii 888 2629 200 10 6 10 WARNING Disconnect primary power prior to servicing ...
Страница 4: ...iv 888 2629 200 10 6 10 WARNING Disconnect primary power prior to servicing ...
Страница 6: ...MRH 2 888 2629 200 10 6 10 WARNING Disconnect primary power prior to servicing ...
Страница 8: ...viii 888 2629 200 10 6 10 WARNING Disconnect primary power prior to servicing ...
Страница 9: ...10 6 10 888 2629 200 ix WARNING Disconnect primary power prior to servicing ...
Страница 10: ...x 888 2629 200 10 6 10 WARNING Disconnect primary power prior to servicing ...
Страница 12: ...xii 888 2629 200 10 6 10 WARNING Disconnect primary power prior to servicing ...
Страница 14: ...xiv 888 2629 200 10 6 10 WARNING Disconnect primary power prior to servicing ...
Страница 18: ...Table of Contents Continued 4 ...
Страница 296: ...B 20 888 2629 200 10 6 10 WARNING Disconnect primary power prior to servicing Maxiva ULX COFDM Series ...