10/6/10
888-2629-200
2-53
WARNING: Disconnect primary power prior to servicing.
Section 2 Installation
Maxiva ULX COFDM Series
STEP 4
Press pump select button for PUMP A ON then PUMP B ON.
The
pumps should switch. This is indicated on the TCU GUI screen (pump
that is on is colored green) as well as in the Cooling Control Panel status
light indicators. Monitor the flow produced by each pump when it is
activated.
STEP 5
Switch the LOCAL/REMOTE switch on the control panel to
LOCAL.
Then use the Pump Select switch on the cooling control panel
to switch pumps ON and OFF. The pump that was in standby should
activate after pressing the Pump Select button.
STEP 6
Select REMOTE on the Cooling Control panel.
STEP 7
Go to the GUI SYSTEM screen and select AUTO.
STEP 8
Reduce coolant flow to the cabinet by closing the globe or ball valve
on the inlet hose.
The pump should switch as the flow limit is reached
when flow remains low the pumps should shut down.
STEP 9
After verification of pump switching performance and flow
protection restore the globe or ball valve to it’s previous condition to
restore flow.
2.14.1.3 Normal Pump and Fan Operation
In normal operation (Cooling Control Panel System Control set to REMOTE and Heat
Exchanger Fans set to AUTO), the transmitter commands the pump selection and Fan
operation. If there is a need for operating the pumps or fans independently from the
transmitter, the Local switch position on the Cooling Control Panel System Control
should be selected. If the fans need to be operated independently then MANUAL
should be selected on the Heat Exchanger Fans switch. The coolant level can be easily
checked by viewing the sight tube located above the system air purger.
2.14.1.4 Operational Pressure Values (typical)
Transmitter input:
23.4 psi
Transmitter output:
15.1 psi
Botttom of filter:
34.25 psi
Heat exchanger input:
9 psi
Heat exchanger output:
38.5 psi
Содержание Maxiva ULX
Страница 2: ...ii 888 2629 200 10 6 10 WARNING Disconnect primary power prior to servicing ...
Страница 4: ...iv 888 2629 200 10 6 10 WARNING Disconnect primary power prior to servicing ...
Страница 6: ...MRH 2 888 2629 200 10 6 10 WARNING Disconnect primary power prior to servicing ...
Страница 8: ...viii 888 2629 200 10 6 10 WARNING Disconnect primary power prior to servicing ...
Страница 9: ...10 6 10 888 2629 200 ix WARNING Disconnect primary power prior to servicing ...
Страница 10: ...x 888 2629 200 10 6 10 WARNING Disconnect primary power prior to servicing ...
Страница 12: ...xii 888 2629 200 10 6 10 WARNING Disconnect primary power prior to servicing ...
Страница 14: ...xiv 888 2629 200 10 6 10 WARNING Disconnect primary power prior to servicing ...
Страница 18: ...Table of Contents Continued 4 ...
Страница 296: ...B 20 888 2629 200 10 6 10 WARNING Disconnect primary power prior to servicing Maxiva ULX COFDM Series ...