WARNING: Disconnect primary power prior to servicing.
Maxiva ULX COFDM Series
copper-clad steel, a minimum of eight feet (2.5 meters) in length and spaced apart not
more than twice the rod length. Brazing or welding should be used for permanent
connections between these items.
Where a resistance of 10 ohms cannot be obtained with the above configuration,
alternate methods must be considered.
Ideally, the best building ground plane is an equipotential ground system. Such a plane
exists in a building with a concrete floor if a ground grid, connected to the facility
ground system at multiple points, is embedded in the floor.
The plane may be either a solid sheet or wire mesh. A mesh will act electrically as a
solid sheet as long as the mesh openings are less than 1/8 wavelength at the highest
frequencies of concern. When it is not feasible to install a fine mesh, copper-clad steel
meshes and wires are available. Each crossover point must be brazed to ensure good
electrical continuity. Equipotential planes for existing facilities may be installed at or
near the ceiling above the equipment.
Each individual piece of equipment must be bonded to its rack or cabinet, or have its
case or chassis bonded to the nearest point of the equipotential plane. Racks and
cabinets should also be grounded to the equipotential plane with a copper strap.
RF transmission line from the antenna must be grounded at the entry point to the
building with 2 or 4 inch copper strap. Wire braid or fine-stranded wire must not be
used.
All building main metallic structural members such as columns, wall frames, roof
trusses, and other metal structures must be made electrically continuous and grounded
to the facility ground system at multiple points. Rebar, cross over points, and vertical
runs should also be made electrically continuous and grounded.
Conduit and power cable shields that enter the building must be bonded at each end to
the facility ground system at each termination.
Содержание Maxiva ULX
Страница 2: ...ii 888 2629 200 10 6 10 WARNING Disconnect primary power prior to servicing ...
Страница 4: ...iv 888 2629 200 10 6 10 WARNING Disconnect primary power prior to servicing ...
Страница 6: ...MRH 2 888 2629 200 10 6 10 WARNING Disconnect primary power prior to servicing ...
Страница 8: ...viii 888 2629 200 10 6 10 WARNING Disconnect primary power prior to servicing ...
Страница 9: ...10 6 10 888 2629 200 ix WARNING Disconnect primary power prior to servicing ...
Страница 10: ...x 888 2629 200 10 6 10 WARNING Disconnect primary power prior to servicing ...
Страница 12: ...xii 888 2629 200 10 6 10 WARNING Disconnect primary power prior to servicing ...
Страница 14: ...xiv 888 2629 200 10 6 10 WARNING Disconnect primary power prior to servicing ...
Страница 18: ...Table of Contents Continued 4 ...
Страница 296: ...B 20 888 2629 200 10 6 10 WARNING Disconnect primary power prior to servicing Maxiva ULX COFDM Series ...