Network Configuration
51
•
•
•
•
•
•
5. Run the Modbus Function code #4 (read multiple registers). This will allow the
user to read the status of the command in data register #1.
If you wish to then read back the value you have written:
6. Enter the command #0 into data register #0.
7. Run the Modbus Function code #16 (write multiple registers), or Function code
#6 (write single register) insuring the correct data location is being set.
8. Run the Modbus Function code #4 (read multiple registers).
Read the value for the span parameter in data registers #4 & 5. This value will be in
floating point format.
Profibus-DP
The Profibus®-DP (Decentralized Peripherals) communication profile is designed for
efficient field-level data exchange. Central automation devices, such as PLC/PC or process
control systems, communicate through a fast serial (RS-485) connection with distributed
field devices, e.g. PLCs. To begin communicating weighing parameters between an HI
6000 Series controller and a PLC, PC or DCS system controller, you need only to load the
*.GSD file and set the node address.
Wiring
For Profibus, connect the two wires to pins 3 and 4.
Profibus Configuration
Profibus-DP operates using a cyclic transfer of data between master(s) and slave(s) on an
RS-485 network. An assigned master periodically requests (polls) each node (slave) on the
network. The HI 6500 or HI 6510 is a slave device. All data communication exchanges
between a master and the HI 6500 or 6510 originate from the master device. Each HI 6500
or HI 6510 is assigned to one master and only that master may write output data to that HI
6500 or HI 6510. Other masters may read information from any slave, but can only write
output data to their own assigned slaves.
Because Profibus uses a cyclic (periodic) polling mechanism between masters and slaves,
it is also deterministic. Therefore, behavior of a Profibus system can be reliably predicted
over time. Profibus is designed to guarantee a deterministic response.
The length (and timing) of the I/O data to be transferred from a single slave to a master is
predefined in the slave's device data base or GSD file. The GSD files of each device
connected via the network (slaves and class 1 masters only) are compiled into a master
parameter record which contains parameterization and configuration data, an address
Содержание HI 6500 Series
Страница 10: ...viii Contents ...
Страница 20: ...10 Chapter 2 ...
Страница 72: ...62 Chapter 4 ...
Страница 96: ...86 Chapter 5 Profibus DP Commands and Parameters ...
Страница 97: ...Instrument Configuration 87 Serial Option Termination ...
Страница 126: ...116 Chapter 5 ...
Страница 156: ...146 Chapter 8 ...
Страница 163: ...Troubleshooting 153 General Troubleshooting Flow Chart Index ...
Страница 164: ...154 Chapter 9 A Guideline Instability Electrical and Mechanical review ...
Страница 165: ...Troubleshooting 155 A1 Checking for Unstable Components in a Weighing System ...
Страница 166: ...156 Chapter 9 B Guidelines for Electrical Mechanical or Configuration Issues ...
Страница 167: ...Troubleshooting 157 B1 Guidelines to Verify Electrical Installation ...
Страница 168: ...158 Chapter 9 B2 Guidelines to Verify Mechanical Installation ...
Страница 169: ...Troubleshooting 159 B3 Guidelines to Verify Configuration Filter Settings to Improve Stability ...
Страница 170: ...160 Chapter 9 C Integrated Technician and Stability Test Overview ...
Страница 171: ...Troubleshooting 161 E Testing for Non Return to Zero System with IT Summing Card ...
Страница 173: ...Troubleshooting 163 G Calibration Errors When Performing the Calibration ...
Страница 174: ...164 Chapter 9 H Mechanical Installation ...
Страница 175: ...Troubleshooting 165 J Electrical Inspection ...
Страница 176: ...166 Chapter 9 K Installation Check Points ...
Страница 177: ...Troubleshooting 167 M Weight Processor s Front Display is Blank or Locked ...
Страница 178: ...168 Chapter 9 N Analog Out HI 6510 Only ...
Страница 194: ...184 Appendix A Figure D1 Assembling the Swivel Mount Enclosure on the instrument pedestal ...
Страница 195: ...Installation of Swivel Mount Enclosures 185 Figure D2 Assembling the Swivel Mount Enclosure on a Table ...
Страница 196: ...186 Appendix A Dimensions ...
Страница 200: ...4 HI 6500 Series USER GUIDE Index ...
Страница 201: ......