Hampton
®
H27E-11DirectVentFreestandingGasStove
| 35
installation
Note: If you are using a 6" square
support you may find it difficult
to screw it in place because it is
fairly small inside.
Simpson Dura-Vent has provided angle
bracketswiththissupportwhichcanbe
screwed to the outside of the support
boxandnailedtosurroundingframingas
required.Useaminimumoffour#8x1/2"
screwsperbracket.Insomecasesthese
brackets may need to be trimmed (e.g.:
tofitunderaflashing).PlacetheFinish
Collararoundthesupportandfastenitto
theceilingusingthescrewsprovided.
3) Use appropriate roof flashing. Place the
flashingundertheuppershinglesandon
topofthelowershinglesapproximatelyhalf
oftheflashingshouldbeundertheshingles.
4) Assemble the desired lengths of Black
PipeandElbowsnecessarytoreachfrom
theapplianceadapterupthroughthesup-
portboxandflashingtoproperheightas
perDia.12,localcodesorinthe"Venting
Arrangement"section.Ensurethatallpipe
andelbowconnectionsareintheirfullytwist
lockposition.
5) Ensureventisverticalandsecureflashingto
theroofwithroofingnails.Slidethestorm
collaroverthepipesectionandsealwitha
mastic.
6) Twistlocktheventcapontothelastsection.
Support Extensions - Round
(RDSE)
or Square (SQSE)
Steep pitched cathedral ceilings may require
theuseofasupportextension.Thispiecefits
downinsidethesupportandcanbeadjusted
toincreasethesupport'slengthbyupto22".
Theextensionisattachedtothesupportusing
theeightmetalscrewsprovided.Besurethere
isatleasta2inchoverlapwheretheextension
joinsthesupport.
High Elevation
ThisunitisapprovedinCanadaforaltitudeto
4500ft.(CAN/CGA-2.17-M91).ForNaturalGas
installationsabove4500ft.followcurrentCAN/
CGA-B149.1.
Gas Connection
Thegasconnectionisa3/8"NPT90
o
elbow.The
gaslinecanberigidpipeortomakeinstallation
easier, use a listed flexible connector and/or
coppertubingifallowedbylocalcodes.
SYSTEM DATA - H27E-11
For 0 to 4500 feet altitude
Burner Inlet Orifice Sizes:
Natural Gas Propane
Burner #42 #54
Max. Input Rating
- Natural Gas
25,000 Btu/h
- Propane
23,000 Btu/h
Min. Input Rating
- Natural Gas
12,500 Btu/h
- Propane
11,500 Btu/h
Supply Pressure
Natural Gas
min. 5.0" w.c.
Propane
min. 12.0" w.c.
Manifold Pressure
Natural Gas
3.5" w.c.
Propane
10" w.c.
8) Ensureventisverticalandsecurethebaseof
theflashingtotheroofwithroofingrails,slide
stormcollaroverthepipesectionandsealwith
amastic.
9) Installtheverticalterminationcapbytwistlocking
it.
Notes:
a)
For multistory vertical installations, a Ceil-
ing Fire stop is required at the second floor,
and any subsequent floor. Diagram 12. The
opening should be framed to 10 " x 10" inside
dimensions, in the same manner as shown
in diagram 9.
b)
Any occupied areas above the first floor,
including closets and storage spaces,
through which the vertical vent passes, must
be enclosed.
Cathedral Ceilings
Round Support (RDS) &
Square Support (SQS)
If your home has a cathedral ceiling (no attic
spacebetweentheceilingandtheroof),install
thechimneyandsupportasfollows.
1) Situatethechimneyinaconvenientlocationas
nearaspossibletotheapplianceoutlet.Cut
andframeaholeintheroofforthesupport.
Thesidesofthisholemustbeverticalwith1
1/4"clearance.
2) Placethesupportintheopening.Loweritto
thecorrectheightasdeterminedbythetable
anddiagrambelow.
Usingalevel,makesurethesupportisverti-
cal.Ifthesupportextendsabovetheroof,
cutitflushwiththetopoftheroof.Nailthe
support to the frame opening using (8) 3"
spiralnailsor#8x1-1/2"screws.
Slope
"X"
0/12 -2/12
4"
2/12 -7/12
5-1/2"
7/12 -12/12
6-3/4"
12/12 -24/12
7-1/2"
24/12+
12-1/2"
Since some municipalities have additional local
codesitisalwaysbesttoconsultwithyourlocalau-
thoritiesandtheCAN/CGAB149installationcodes.
ForUSAinstallationsfollowlocalcodesand/orthe
currentNationalFuelGasCode,ANSIZ223.1.
When using copper or flex connectors use only
approvedfittings.Alwaysprovideaunionsothat
gas lines can be easily disconnected for burner
and/orvalveservicing.Flarenutsforcopperlines
andflexconnectorsareusuallyconsideredtomeet
thisrequirement.
IMPORTANT: ALWAYS CHECK FOR
GAS LEAKS WITH A SOAP AND WATER
SOLUTION OR GAS LEAK DETECTOR.
DO NOT USE OPEN FLAME FOR LEAK
TESTING.
Note: Prior to any pressure testing of
the gas supply piping system that
exceeds test pressures of 1/2 psig,
this appliance must be disconnected
from the piping system. If test pres-
sures equal to or less than 1/2 psig
are used then this appliance must
be isolated from the piping system
by closing its individual manual
shut-off valve during the testing.
Содержание H27
Страница 51: ...Hampton H27E 11 Direct Vent Freestanding Gas Stove 51 notes...
Страница 56: ...56 Hampton H27E 11 Direct Vent Freestanding Gas Stove warranty...
Страница 57: ...Hampton H27E 11 Direct Vent Freestanding Gas Stove 57 notes...
Страница 58: ...58 Hampton H27E 11 Direct Vent Freestanding Gas Stove notes 58...
Страница 59: ...Hampton H27E 11 Direct Vent Freestanding Gas Stove 59...