113
SCADA-Modbus
®
System Guidelines
Query
The Modbus ASCII query must take the form shown below that specifies the starting
register and number of registers to be read:
Table 44 SCADA-Modbus Units of Measure Codes
Unit
Code
Unit
Code
ML 1
GPH
26
AF 2
LPS
27
CF 3 LPM
28
GAL 4 LPH 29
L 5
MGD
30
M3 6 PH 31
IN 7
ORP
32
CM 8 PPM
33
FT 9
PPB
34
M 10 MGL 35
CM2 11
PCTSAT
36
FT2 12
MSIEMENS
37
IN2
13 MICROSIEMENS 38
M2
14 GRAMSPERKG 39
AFD 15
PCTPERDEGC
40
CFS 16
DEGREE_C
41
CFM 17
DEGREE_F
42
CFH 18
MILS 43
CFD 19
VOLTS
44
CMS 20
FPS 45
CMM 21
MPS 46
CMH 22
PCT_O2
47
CMD 23
PCT_H2S
48
GPS 24
PCT_LEL
49
GPM 25
VDC 50
Start
‘:’
Slave
Address
Function
(03)
Start
Address
High
Start
Address
Low
No. of Pts.
High
No. of.
Pts. Low
LRC
<CR>
<LF>
Содержание Sigma 950
Страница 2: ......
Страница 6: ...4...
Страница 20: ...18 Introduction...
Страница 34: ...32 Basic Programming Setup...
Страница 50: ...48 Sensor Installation...
Страница 82: ...80 Maintenance...
Страница 83: ...81 Appendix A Program Flow Charts Figure 22 Overview of Basic Program Menus...
Страница 84: ...82 Program Flow Charts Figure 23 Setup Flow Chart...
Страница 85: ...83 Program Flow Charts Figure 24 Options Flow Chart...
Страница 86: ...84 Program Flow Charts Figure 25 Alarms Menus Flow Chart...
Страница 87: ...85 Program Flow Charts Figure 26 Calibration Menus Flow Chart Page 1...
Страница 88: ...86 Program Flow Charts...
Страница 102: ...100 Programming Features...
Страница 106: ...104 Primary Devices Head Measurement Locations...
Страница 126: ...124 SCADA Modbus System Guidelines...