MG510R Calibration
26
W450256 Rev A 06/07
Menu 10 - Erected attachments
This menu is used to calibrate attachment radii, moments, and dimensions. For systems without pre-
calibrated flys, perform a calibration routine on each jib configuration.
Before starting this procedure you must
configure the jib or attachment while in normal
operation mode. You can not adjust or erect a jib
while in calibration mode.
Press the key adjacent to either “Menu Up” or “Menu Down” until “10 Erected Attachments” appears
in the information window at the right.
TEST
SET
Press the key adjacent to “10 Erected Attachments” to enter the routine.
Upon starting the procedure the editor can be used to enter supplied calibration data manually to
avoid performing the entire calibration routine. It can also be used to trim calibrations that are less
than perfect.
For each fly/jib combination, the system must gather data about the jib moment (taken from the
pressure sensors) and the jib radius (taken from manual measurements, use the measurements
recorded in Appendix A). Data must be gathered with the boom fully extended at high and low boom
angles, and fully retracted at high and low boom angles.
Enter the main hook weight. If there is an unused hook block present on the main boom;
1.
otherwise enter 0.0 .
TEST
SET
Enter the weight of the fly hook and any other shackles or rope weights suspended from the fly
2.
pick point.
TEST
SET
Select proper fly/jib
configuration
Содержание MicroGuard 510 Retrofit
Страница 1: ...MicroGuard 510 Retrofit Rated Capacity Indicator System Calibration...
Страница 2: ......
Страница 40: ...MG510R Calibration 36 W450256 Rev A 06 07...
Страница 46: ...MG510R Calibration A 6 W450256 Rev A 06 07...
Страница 54: ...MG510R Calibration B 8 W450256 Rev A 06 07...
Страница 55: ......