MG510R Calibration
21
W450256 Rev A 06/07
If you are checking an existing calibration, select “No”. You will be prompted to extend the boom to the
necessary length to calibrate, or recalibrate a different length configuration.
If “Yes” is pressed, you will be asked to confirm your request. Press the key adjacent to “Yes”.
TEST
SET
Note: A new calibration will erase any and all radius moment data previously entered.
Enter the tare load (the only weight should be that of the hook block; if there is a block hanging, add
this to the tare). Also, the unit must be configured with a single part line. When entering the tare load
in the calibration routine, adding 100 pounds (0.1) to the actual weight will help guarantee a slightly
positive load reading in all operating configurations.
TEST
SET
Begin with the boom fully retracted and enter the length.
IMPoRTaNT!
Do NoT MovE ThE BooM ExTENsIoN aGaIN DURING ThIs PRoCEss. ThE BooM ExTENsIoN
MUsT REMaIN aT ThE saME lENGTh DURING BoTh ThE hIGh aND loW RaDIUs ChECks.
Press the key adjacent to “OK” key when ready. Enter the radius at these points of calibration.
TEST
SET
TEST
SET
Enter the value for the high radius. Use the keys adjacent to the numerical values at the bottom of the
window to scroll left or right and highlight each number. Use the key adjacent to “Enter Hi Radius” to
enter the number. When complete, the menu will automatically change to the previous menu. To exit
the routine without changes, press the key adjacent to “Exit”. Repeat the procedure to enter the low
radius.
TEST
SET
TEST
SET
Содержание MicroGuard 510 Retrofit
Страница 1: ...MicroGuard 510 Retrofit Rated Capacity Indicator System Calibration...
Страница 2: ......
Страница 40: ...MG510R Calibration 36 W450256 Rev A 06 07...
Страница 46: ...MG510R Calibration A 6 W450256 Rev A 06 07...
Страница 54: ...MG510R Calibration B 8 W450256 Rev A 06 07...
Страница 55: ......