Gree GMV6 HR DC Inverter VRF Units Service Manual
47
4.1.2.2 Function Description
Function
Code
Function Name
Description
Default Setting
Remarks
Code
Meaning
A2
Refrigerant
recycle
This function is automatically
started during maintenance. Based
on the system pressure change,
this function recycles all or partial
refrigerant of the faulty module or
the indoor unit pipeline.
—
—
This function can
only be set.
A6
Cooling/heating of
the entire system
The unit can be set to cooling and
heating, cooling only, heating only,
or fan mode for centralized
management.
nA
Cooling and
heating
This function can
be set and
queried.
A7
Outdoor silence
mode
This function sets different silence
modes based on the user's needs.
00
No silence
This function can
be set and
queried.
A8
After-sales
vacuum pumping
mode
During maintenance, the system
automatically turns on all electronic
expansion valves and solenoid
valves to ensure that all lines can
be vacuumed.
—
—
This function can
only be set.
n0
Auto energy
saving
This function can automatically
reduce power consumption of the
unit based on system operating
parameters.
01
Capability
priority
control
This function can
be set and
queried.
n3
Forced defrosting
This function forcibly enables
defrosting of the outdoor unit of the
system.
—
—
This function can
only be set.
n4
Forced energy
saving
This function forcibly reduces the
maximum power consumption of
the unit.
10
100%
capability
output
This function can
be set and
queried.
n5
Indoor unit
engineering SN
offset
When different refrigerating
systems are controlled in a
centralized manner, this function
avoids the conflict of indoor unit
engineering numbers.
—
—
This function can
only be set.
qJ
One-button
drainage of
dual-heat-source
units
This function opens the water
valves of all dual-heat-source
indoor units in the system.
—
—
This function is
applicable to
drainage in
non-heating
seasons.
C8
Compressor
emergency
setting
—
00
Normal
operation of
the
compressor
—
CA
Module
emergency
setting
—
00
Normal
operation of
the module
—
C9
Fan emergency
setting
—
00
Normal
operation of
the fan
—
1G
Outdoor static
pressure setting
—
00
0 Pa static
pressure
—
Содержание GMVVQ1015WM/C-X
Страница 418: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 416 GMV VQ400WM C X GMV VQ450WM C X...
Страница 419: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 417 GMV VQ504WM C X GMV VQ560WM C X GMV VQ615WM C X...
Страница 420: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 418 NCHS1D...
Страница 421: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 419 NCHS2D...
Страница 422: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 420 NCHS4D...
Страница 423: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 421 NCHS8D...
Страница 426: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 424 6 1 2 Heating Operation...
Страница 427: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 425 6 1 3 Main body Cooling...
Страница 428: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 426 6 1 4 Main body Heating...
Страница 430: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 428 6 2 2 Heating Operation...
Страница 431: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 429 6 2 3 Main body Cooling...
Страница 432: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 430 6 2 4 Main body Heating...
Страница 433: ...JF00304244...