Gree GMV6 HR DC Inverter VRF Units Service Manual
412
Appendix 4 Electric Specifications
Every unit should have corresponding short-circuit and overload protection. And also a main switch
is required to control power supply or disconnection.
Please refer to the following table for outdoor unit power cord specifications and circuit breakers
Model
Combination
method
Power supply
Capacity of
circuit breaker
of each
combination
module (A)
Minimum
cross-sectional
area of grounding
wire (mm
2
)
Recommended wire
(cross-sectional area)
(mm
2
)
GMV-VQ224WM/C-X
-
380-415V 3N~
50/60Hz
25
2.5
2.5×5
GMV-VQ280WM/C-X
-
380-415V 3N~
50/60Hz
25
2.5
2.5×5
GMV-VQ335WM/C-X
-
380-415V 3N~
50/60Hz
25
4.0
4.0×5
GMV-VQ400WM/C-X
-
380-415V 3N~
50/60Hz
40
6.0
6.0×5
GMV-VQ450WM/C-X
-
380-415V 3N~
50/60Hz
40
6.0
6.0×5
GMV-VQ504WM/C-X
-
380-415V 3N~
50/60Hz
50
10.0
10.0×5
GMV-VQ560WM/C-X
-
380-415V 3N~
50/60Hz
50
10.0
10.0×5
GMV-VQ615WM/C-X
-
380-415V 3N~
50/60Hz
50
10.0
10.0×5
GMV-VQ680WM/C-X
280+400
380-415V 3N~
50/60Hz
25+40
2.5+6.0
2.5×5+6.0×5
GMV-VQ730WM/C-X
280+450
380-415V 3N~
50/60Hz
25+40
2.5+6.0
2.5×5+6.0×5
GMV-VQ784WM/C-X
280+504
380-415V 3N~
50/60Hz
25+50
2.5+10.0
2.5×5+10.0×5
GMV-VQ840WM/C-X
280+560
380-415V 3N~
50/60Hz
25+50
2.5+10.0
2.5×5+10.0×5
GMV-VQ895WM/C-X
280+615
380-415V 3N~
50/60Hz
25+50
2.5+10.0
2.5×5+10.0×5
GMV-VQ950WM/C-X
335+615
380-415V 3N~
50/60Hz
25+50
4.0+10.0
4.0×5+10.0×5
GMV-VQ1015WM/C-
X
400+615
380-415V 3N~
50/60Hz
40+50
6.0+10.0
6.0×5+10.0×5
GMV-VQ1065WM/C-
X
450+615
380-415V 3N~
50/60Hz
40+50
6.0+10.0
6.0×5+10.0×5
GMV-VQ1119WM/C-
X
504+615
380-415V 3N~
50/60Hz
50+50
10.0+10.0
10.0×5+10.0×5
Содержание GMVVQ1015WM/C-X
Страница 418: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 416 GMV VQ400WM C X GMV VQ450WM C X...
Страница 419: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 417 GMV VQ504WM C X GMV VQ560WM C X GMV VQ615WM C X...
Страница 420: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 418 NCHS1D...
Страница 421: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 419 NCHS2D...
Страница 422: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 420 NCHS4D...
Страница 423: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 421 NCHS8D...
Страница 426: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 424 6 1 2 Heating Operation...
Страница 427: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 425 6 1 3 Main body Cooling...
Страница 428: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 426 6 1 4 Main body Heating...
Страница 430: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 428 6 2 2 Heating Operation...
Страница 431: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 429 6 2 3 Main body Cooling...
Страница 432: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 430 6 2 4 Main body Heating...
Страница 433: ...JF00304244...