Gree GMV6 HR DC Inverter VRF Units Service Manual
250
4.1.4.1 Mechanical Inspection
Step 1
: Confirm that the unit Power is disconnected.
Step 2
: Find the 4-way valve coil, check whether the fixing screw is loose and whether the valve and
coil have any apparent exceptions.
Step 3
: Energize and turn on the unit, check the temperature of pipelines of 4-way valve under
operating status:
D - Connecting to
the exhaust side.
Warning: high
temperature!
There are labels in the 4-way valve, D refers to connecting exhaust side, S refers to connecting
inhalation side of gas-liquid separator. When the system is operating, check if the temperature of the
pipelines are the same with that of the following table. Note that do not directly touch the pipeline for
avoiding scald!
Operating
mode
4-way valve
Pipeline status
S pipe
E pipe
C pipe
D pipe
Cooling
operation
Cooling
4-way valve
Low
temperature
Low
temperature
High
temperature
High
temperature
Heating
4-way valve
Low
temperature
High
temperature
Low
temperature
High
temperature
Heating
operation
Cooling
4-way valve
Low
temperature
High
temperature
Low
temperature
High
temperature
Heating
4-way valve
Low
temperature
High
temperature
Low
temperature
High
temperature
4.1.4.2 Electrical Inspection
Compare the measured coil resistance with the normal coil resistance to check whether the coil is
damaged.
(
1
)
Power off the unit. Remove the electrical appliance cover after the ODU stops.
Warning:
Electric shock
(
2
)
Remove the electrical appliance cover and check whether the connecting terminal of the
4-way valve is firm.
(
3
)
Disconnect the corresponding valve's coil terminal from the main board and use a multimeter
to measure the coil resistance.
Содержание GMVVQ1015WM/C-X
Страница 418: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 416 GMV VQ400WM C X GMV VQ450WM C X...
Страница 419: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 417 GMV VQ504WM C X GMV VQ560WM C X GMV VQ615WM C X...
Страница 420: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 418 NCHS1D...
Страница 421: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 419 NCHS2D...
Страница 422: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 420 NCHS4D...
Страница 423: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 421 NCHS8D...
Страница 426: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 424 6 1 2 Heating Operation...
Страница 427: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 425 6 1 3 Main body Cooling...
Страница 428: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 426 6 1 4 Main body Heating...
Страница 430: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 428 6 2 2 Heating Operation...
Страница 431: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 429 6 2 3 Main body Cooling...
Страница 432: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 430 6 2 4 Main body Heating...
Страница 433: ...JF00304244...