Gree GMV6 HR DC Inverter VRF Units Service Manual
20
Checklist Before GMV6 HR Commissioning
Category
No.
Item
Reference Value
Qualified
Inspector
Electrical
system
31
Do the power voltage, phase
sequence, and frequency meet the
unit requirements?
The power voltage, phase
sequence, and frequency
are consistent with those on
the unit nameplate, and the
voltage fluctuates within
±10%.
32
Is the power cable more than 1 m
away from a TV?
—
33
Is there any strong electromagnetic
interference, dust, acid and alkaline
gas in the environment where the
unit is located?
—
Communication
system
34
Does the communication cable
material meet the unit design
requirements?
—
35
Is the communication connection
between outdoor unit modules
correct?
—
36
Is the DIP switch of the master unit
of the outdoor unit module correct?
—
37
Is the communication between the
outdoor master unit and the indoor
unit correct?
Serial connection
38
Is the communication connection
between indoor units correct?
—
39
Is the communication connection
between the indoor unit and the
wired controller correct?
—
40
Is the last communication indoor
unit installed with a communication
build-out resistor?
—
41
The communication cable cannot
be laid in the same trough as the
power cable. It is laid separately in
a flame-retardant hard PVC pipe.
The parallel spacing between a
communication cable and a
strong-current cable is greater than
20 cm.
—
Indoor unit
installation
42
Does the indoor unit drain pipe
have a slope of 1/100?
—
43
Does the height of the indoor unit
riser drain pipe meet the
requirements?
—
44
Does the indoor unit drain
smoothly?
—
45
Is there a U-shaped trap for indoor
unit drainage?
—
46
Is there a soft joint at the air outlet
and air return vent of the indoor
unit? Does the return air have a
static pressure box?
—
47
Does the indoor unit water pipe
have an emptying port?
—
48
Is a "main" label attached to the
wired controller or panel of the main
indoor unit?
—
Содержание GMVVQ1015WM/C-X
Страница 418: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 416 GMV VQ400WM C X GMV VQ450WM C X...
Страница 419: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 417 GMV VQ504WM C X GMV VQ560WM C X GMV VQ615WM C X...
Страница 420: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 418 NCHS1D...
Страница 421: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 419 NCHS2D...
Страница 422: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 420 NCHS4D...
Страница 423: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 421 NCHS8D...
Страница 426: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 424 6 1 2 Heating Operation...
Страница 427: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 425 6 1 3 Main body Cooling...
Страница 428: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 426 6 1 4 Main body Heating...
Страница 430: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 428 6 2 2 Heating Operation...
Страница 431: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 429 6 2 3 Main body Cooling...
Страница 432: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 430 6 2 4 Main body Heating...
Страница 433: ...JF00304244...