Gree GMV6 HR DC Inverter VRF Units Service Manual
141
Yes
No
"F0" Poo r Main Bo ard of
the Outdoor Unit
Whether syste m clock exce ptio n
is a lso gen erated (check by u sin g the
commissionin g software)?
Replace th e CPU
(sma ll b oard)
No
Replace th e compre ssor
drive boar d
Add ress ch ip and me mo ry
chip are abno rma l
Yes
Replace th e main control
boa rd
Is th e p roblem so lve d after the
CPU (sma ll b oard) is re placed?
No